Technical Details

Operating Manual PSSu H F PN
22071-EN-06

20

Environmental data

312043

Airgap creepage

In accordance with the standard

EN 60664-1

Overvoltage category

II

Pollution degree

2

Protection type

Mounting (e.g. cabinet)

IP54

Housing

IP20

Mechanical data

312043

Material

Bottom

PC

Front

PC

Dimensions

Height

128,4 mm

Width

75,2 mm

Depth

79,4 mm

Weight

199 g

Safety characteristic data

Operating

mode

EN ISO

13849-1:

2008
PL

EN ISO

13849-1:

2008
Category

EN IEC

62061
SIL CL

EN IEC

62061
PFH

D

[1/h]

IEC 61511
SIL

IEC 61511
PFD

EN ISO

13849-1:

2008
T

M

[year]

PL e

Cat. 4

SIL CL 3

2,88E-09

SIL 3

3,95E-05

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

Information
A safety function's SIL/PL values are

not identical to the SIL/PL values of

the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.

8.1