Operating Manual PSSu H F PN
22071-EN-06

11

PROFINET

Connection to PROFINET

Decentralised input/output

}

The head module enables the PSSuniversal to be used as a modular, decentralised in-

put/output module.

}

The head module receives signals from a master controller; it processes these signals

and passes them on to the connected input/output modules.

}

The head module receives signals from the connected input/output modules; it process-

es these signals and passes them on to a master controller.

Interfaces

}

PROFINET interface with PROFIsafe profile

– The PROFINET interface enables standard data to be exchanged with a master

controller.

– The PROFINET interface with PROFIsafe profile enables data to be transferred

safely between the PSSuniversal and a master controller.

– If a fault occurs, the module switches off the connected failsafe output modules.
– The station address is set via a DIP switch.

All the project data is stored in the head module. The project data can also be stored on a
chip card.

DIP switch for setting the F address

The station address of a PSSu is set via the “F-ADDRESS” DIP switches. The DIP switches
are binary coded. Permitted station addresses are in the range 0

D

... 511

D

.

A station address is set via a combination of the relevant binary coded switches:

“F-ADDRESS” DIP switch

Key

Example

Switch designation

OFF

ON

Station address 52

D

256

0

256

D

F-ADDRESS

OFF ON

128

64

32

16

8

4

2

1

256

128

0

128

D

64

0

64

D

32

0

32

D

16

0

16

D

8

0

8

D

4

0

4

D

2

0

2

D

1

0

1

D

4.2

4.2.1

4.2.2