2 profinet, 1 connection to profinet, 2 dip switch for setting the f address – Pilz PSSu H F PN User Manual
Page 11: Profinet, Connection to profinet, Dip switch for setting the f address

Function description
Operating Manual PSSu H F PN
22071-EN-06
11
PROFINET
Connection to PROFINET
Decentralised input/output
}
The head module enables the PSSuniversal to be used as a modular, decentralised in-
put/output module.
}
The head module receives signals from a master controller; it processes these signals
and passes them on to the connected input/output modules.
}
The head module receives signals from the connected input/output modules; it process-
es these signals and passes them on to a master controller.
Interfaces
}
PROFINET interface with PROFIsafe profile
– The PROFINET interface enables standard data to be exchanged with a master
controller.
– The PROFINET interface with PROFIsafe profile enables data to be transferred
safely between the PSSuniversal and a master controller.
– If a fault occurs, the module switches off the connected failsafe output modules.
– The station address is set via a DIP switch.
All the project data is stored in the head module. The project data can also be stored on a
chip card.
DIP switch for setting the F address
The station address of a PSSu is set via the “F-ADDRESS” DIP switches. The DIP switches
are binary coded. Permitted station addresses are in the range 0
D
... 511
D
.
A station address is set via a combination of the relevant binary coded switches:
“F-ADDRESS” DIP switch
Key
Example
Switch designation
OFF
ON
Station address 52
D
256
0
256
D
F-ADDRESS
OFF ON
128
64
32
16
8
4
2
1
256
128
0
128
D
64
0
64
D
32
0
32
D
16
0
16
D
8
0
8
D
4
0
4
D
2
0
2
D
1
0
1
D
4.2
4.2.1
4.2.2