1 safety characteristic data, Safety characteristic data – Pilz PSSu H PLC1 FS DP SN SD User Manual
Page 38
Technical details
Operating Manual PSSu H PLC1 FS DP SN SD
1001776EN04
38
Environmental data
312071
Airgap creepage
In accordance with the standard
EN 606641
Overvoltage category
II
Pollution degree
2
Protection type
Mounting area (e.g. control cabinet)
IP54
Housing
IP20
Mechanical data
312071
Material
Bottom
PC
Conductor cross section with screw terminals
1 core flexible
0,25 2,50 mm², 24 12 AWG
2 core with the same cross section, flexible with
crimp connectors, no plastic sleeve
0,25 1,00 mm², 24 16 AWG
2 core with the same cross section, flexible without
crimp connectors or with TWIN crimp connectors
0,20 1,50 mm², 24 16 AWG
Torque setting with screw terminals
0,50 Nm
Connection type
Springloaded terminal, screw terminal
Mounting type
plugin
Conductor cross section with springloaded terminals:
Flexible with/without crimp connector
0,20 2,50 mm², 24 12 AWG
Stripping length
9 mm
Dimensions
Height
125,6 mm
Width
130,0 mm
Depth
83,7 mm
Weight
405 g
The standards current on 200907 apply.
9.1
Safety characteristic data
Operating
mode
EN ISO
138491:
2008
PL
EN ISO
138491:
2008
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
138491:
2008
T
M
[year]
–
PL e
Cat. 4
SIL CL 3
4,14E09
SIL 3
3,51E05
20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.