Function description

Operating Manual PSSu H PLC1 FS DP SN SD
1001776­EN­04

14

MAC address

}

The MAC address is a factory­set default. It can found on the labelling strip on the front
of the module.

INFORMATION

Further information on SafetyNET p can be found in the "PSS 4000 System
Description".

4.3

PROFIBUS DP

4.3.1

Connection to PROFIBUS DP

PROFIBUS is an open fieldbus standard whose communication is defined in the interna­
tional standards IEC 61158 and IEC 61784. Further provisions have been defined in spe­
cifications published by the PROFIBUS User Group. These specifications are available
from PROFIBUS International (see www.profibus.com).

4.3.2

Selector switch for setting the station address

The station address is set via the "ADDRESS" DIP switch. The DIP switch is binary coded.
Permitted station addresses are in the range 0

D

 ... 125

D

. If station address 126

D

 is set via

the DIP switch, the address can be assigned via the Master. The Set Slave Address com­
mand (SSA) must be run for this purpose.

The station address is set as follows:

"ADDRESS" DIP switch

Meaning

Example:

Switch designation

OFF

ON

Station address

PSSu: 26 

D

F­device: 52 

D

­ ­

Not connected

ADDRESS

OFF

ON

- -

64
32
16

8
4
2
1

- -

­ ­

64

0

64

D

32

0

32

D

16

0

16

D

8

0

8

D

4

0

4

D

2

0

2

D

1

0

1

D