3 profibus dp, 1 connection to profibus€dp, 2 selector switch for setting the station address – Pilz PSSu H PLC1 FS DP SN SD User Manual
Page 14: Profibus dp, Connection to profibus dp, Selector switch for setting the station address, 1 connection to profibus dp
Function description
Operating Manual PSSu H PLC1 FS DP SN SD
1001776EN04
14
MAC address
}
The MAC address is a factoryset default. It can found on the labelling strip on the front
of the module.
INFORMATION
Further information on SafetyNET p can be found in the "PSS 4000 System
Description".
4.3
PROFIBUS DP
4.3.1
Connection to PROFIBUS DP
PROFIBUS is an open fieldbus standard whose communication is defined in the interna
tional standards IEC 61158 and IEC 61784. Further provisions have been defined in spe
cifications published by the PROFIBUS User Group. These specifications are available
from PROFIBUS International (see www.profibus.com).
4.3.2
Selector switch for setting the station address
The station address is set via the "ADDRESS" DIP switch. The DIP switch is binary coded.
Permitted station addresses are in the range 0
D
... 125
D
. If station address 126
D
is set via
the DIP switch, the address can be assigned via the Master. The Set Slave Address com
mand (SSA) must be run for this purpose.
The station address is set as follows:
"ADDRESS" DIP switch
Meaning
Example:
Switch designation
OFF
ON
Station address
PSSu: 26
D
Fdevice: 52
D
Not connected
ADDRESS
OFF
ON
- -
64
32
16
8
4
2
1
- -
64
0
64
D
32
0
32
D
16
0
16
D
8
0
8
D
4
0
4
D
2
0
2
D
1
0
1
D