Blower drive sheaves – WaterFurnace Envision (XL) User Manual
Page 36

ENVISION 7-25 TONS INSTALLATION MANUAL
37
Multistate Input (Type 13)
13:1 Effective Occupancy
[Read, shows the occupancy status of the heat
pump. 1=Occupied, 2=Unoccupied, 3=Bypass
(temporary
occupancy)]
13:2 Mode
[Read, shows heat pump as normal or emergency
shutdown 1=Auto(normal), 7=Off(shutdown)]
13:3 Compressor/Blower Prove
[Read, shows the contact status of BI-4.]
Multistate Output (Type 14)
14:1 Occupancy Command
[Read/Write, controls the occupancy mode of the
heat Pump. 1=Occupied, 2=Unoccupied, 3=Bypass
(Temporary Occupancy), 4=Standby,
255=Uncommanded]
14:2 Blower Command (G)
[Read/Write, network command to run the blower]
14:3 Comp1 Command (Y1)
[Read/Write, network Y1 command (compressor
1
call).]
14:4 Comp2 Command (Y2)
[Read/Write, network Y2 command (compressor
2
call).]
14:5 Rev Vlv Cmd (O)
[Read/Write, network O command. 1= heating,
2=
cooling.]
14:6 Emergency Override
[Read/Write, provide means of emergency
shutdown]
14:7 Alarm Reset
[Read/Write, allows remote reset of manual reset
alarms, Command to a ‘2’ value for reset action,
1 for normal Operation.]
14:8 BO5 ElectHeat
[Read/Write, network command to enable electric
heat (interlocked with BI4)]
14:9 BO9 Spare
[Read/Write, network command to enable/disable
BO9]
Optional FX10 Microprocessor Control - BACnet Variables cont.