beautypg.com

Ad c e, Nlh080 - blower performance data – WaterFurnace Envision (XL) User Manual

Page 22

background image

ENVISION 7-25 TONS INSTALLATION MANUAL

23

Airflow in CFM with dry coil and clean air filter.

Rated CFM

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

4.0

5.0

5.0

5.0

5.0

2200

BHP

0.37

0.40

0.43

0.47

0.52

0.59

0.65

0.71

0.75

0.78

0.81

0.86

0.90

RPM

583

624

665

706

747

770

791

821

865

911

957

986

1015

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

3.0

2.0

1.0

0.0

3.5

3.0

2.5

2.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

4.0

4.0

4.0

4.0

5.0

5.0

5.0

5.0

5.0

2400

BHP

0.45

0.49

0.53

0.59

0.62

0.67

0.70

0.74

0.79

0.85

0.88

0.91

0.95

1.08

RPM

582

623

664

705

746

765

790

820

861

906

938

970

1004

1030

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

3.0

2.0

1.0

0.0

4.0

3.0

2.5

2.0

1.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

2600

BHP

0.51

0.56

0.62

0.66

0.69

0.73

0.76

0.84

0.90

0.93

0.96

1.04

1.12

1.17

RPM

602

643

684

726

760

783

805

853

877

916

954

988

1021

1051

TURNS OPEN

4.5

3.5

2.5

1.5

4.0

3.5

2.5

2.0

1.5

3.5

3.0

2.5

1.5

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

2800

BHP

0.53

0.58

0.64

0.69

0.76

0.79

0.80

0.94

0.99

1.03

1.15

1.16

1.17

1.27

RPM

581

622

663

704

744

776

802

851

876

900

951

976

1001

1033

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

3.5

3.0

2.0

1.5

1.0

3.0

2.5

2.0

1.5

MTR/SHEAVE

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

3000

BHP

0.59

0.66

0.73

0.80

0.87

0.90

0.92

1.07

1.08

1.10

1.30

1.33

1.35

1.40

1.44

RPM

580

621

662

702

743

775

801

848

873

898

949

973

997

1022

1046

TURNS OPEN

5.0

4.0

3.0

2.0

1.0

3.5

3.0

2.0

1.5

1.0

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

3200

BHP

0.72

0.81

0.90

0.98

1.02

1.04

1.19

1.21

1.23

1.44

1.47

1.51

1.54

1.57

RPM

620

661

701

741

773

799

846

871

895

946

970

994

1019

1043

TURNS OPEN

4.0

3.0

2.0

1.0

3.5

3.0

2.0

1.5

1.0

3.0

2.5

2.0

1.5

1.0

MTR/SHEAVE

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

5.0

5.0

5.0

5.0

5.0

3400

BHP

0.87

0.98

1.08

1.12

1.16

1.31

1.34

1.36

1.58

1.62

1.65

1.69

1.73

RPM

660

700

740

772

797

844

869

893

944

968

992

1016

1040

TURNS OPEN

3.0

2.0

1.0

3.5

3.0

2.0

1.5

1.0

3.0

2.5

2.0

1.5

1.0

Bold Face Requires Larger 2 HP Motor

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 2.5 turns open (2600 cfm @ 0.4 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 1.5 turns open (2600 cfm @ 0.5 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12in. wg.

A

D

C

E

07/25/07

NLH080 - Blower Performance Data

Belt Drive