Installing vertical units, Mounting vertical units, Duct system – WaterFurnace Envision (XL) User Manual

Page 10: Condensate drain

background image

ENVISION 7-25 TONS INSTALLATION MANUAL

11

Control Box

Condensate
Drain

Water Supply
and Return
Connections

Flexible duct
Collar

ACCESS

PA

NE

L

ACCESS

PA

NEL

PAN

EL

AC

CES

S

Figure 6: Typical Vertical Application

Installing Vertical Units

Mounting Vertical Units

Units are available with top/side discharge, left-hand or right-hand return air configurations. Vertical units are assembled on

rails which facilitate moving and placement of the units. It is not necessary to anchor the unit to the floor.

Duct System

A supply air duct flange is provided for field installation to facilitate the secure duct connection at the job site. A flexible

connector is recommended for discharge and return air duct connections on metal duct systems to prevent vibration

transmission. It is recommended that all ductwork be insulated with a minimum of 1/2-inch coated insulation. Installation of

the units with uninsulated ductwork in an unconditioned space is not recommended, as the system’s performance will be

adversely affected.

Condensate Drain

In vertical units, the internal condensate drain assembly consists of a flexible drain tube which is attached to the drain pan

and a 3/4-inch (7-10 tons) and 1-inch (13-25 tons) female pipe thread. An external water trap is not required as the drain

tube serves as a trapping loop. The field-installed piping and unit connection must be properly installed and sealed to

prevent water leakage.