ENVISION 7-25 TONS INSTALLATION MANUAL
24
Airflow in CFM with dry coil and clean air filter.
Rated CFM
External Static Pressure (in. w.g.)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.2
1.4
1.6
1.8
2.0
MTR/SHEAVE
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
4.0
4.0
4.0
4.0
5.0
2600
BHP
0.44
0.47
0.52
0.57
0.66
0.78
0.79
0.80
0.92
0.97
1.08
1.18
1.37
1.56
RPM
584
625
667
708
757
806
831
856
905
960
1021
1082
1142
1202
TURNS OPEN
5.0
4.0
3.0
2.0
4.0
3.0
2.5
2.0
1.0
3.0
2.0
1.0
0.0
3.0
MTR/SHEAVE
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
4.0
4.0
4.0
4.0
5.0
5.0
2800
BHP
0.51
0.56
0.61
0.67
0.77
0.89
0.90
0.91
1.06
1.11
1.14
1.38
1.44
1.59
1.73
RPM
583
625
665
707
756
804
829
854
902
933
982
1055
1100
1156
1212
TURNS OPEN
5.0
4.0
3.0
2.0
4.0
3.0
2.5
2.0
1.0
3.5
2.5
1.5
0.5
3.5
2.5
MTR/SHEAVE
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
3000
BHP
0.57
0.64
0.70
0.76
0.87
1.00
1.01
1.03
1.19
1.25
1.28
1.33
1.59
1.64
1.68
1.91
RPM
582
624
665
705
754
802
827
852
900
930
955
1005
1078
1110
1169
1228
TURNS OPEN
5.0
4.0
3.0
2.0
4.0
3.0
2.5
2.0
1.0
3.5
3.0
2.0
0.5
0.0
3.0
2.0
MTR/SHEAVE
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
3200
BHP
0.70
0.78
0.86
0.97
1.11
1.13
1.15
1.31
1.31
1.38
1.44
1.61
1.69
1.80
2.02
RPM
623
664
704
753
801
826
851
899
919
949
978
1036
1086
1137
1196
TURNS OPEN
4.0
3.0
2.0
4.0
3.0
2.5
2.0
1.0
4.0
3.5
3.0
2.5
1.5
3.5
2.5
MTR/SHEAVE
2.0
2.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
3400
BHP
0.85
0.94
1.07
1.21
1.24
1.26
1.42
1.43
1.50
1.57
1.65
1.71
1.76
2.10
2.35
RPM
663
703
752
800
825
849
896
917
947
976
1020
1057
1094
1164
1223
TURNS OPEN
3.0
2.0
4.0
3.0
2.5
2.0
1.0
4.0
3.5
3.0
2.5
1.8
1.0
3.0
2.0
MTR/SHEAVE
2.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
3600
BHP
1.01
1.16
1.31
1.34
1.37
1.54
1.55
1.63
1.70
1.78
1.87
2.06
2.15
2.40
RPM
702
751
798
823
848
894
915
945
974
1003
1031
1088
1133
1191
TURNS OPEN
2.0
4.0
3.0
2.5
2.0
1.0
4.0
3.5
3.0
2.5
2.0
1.5
3.5
2.5
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
3800
BHP
1.23
1.40
1.44
1.48
1.66
1.67
1.75
1.83
1.91
2.00
2.10
2.19
2.44
RPM
750
797
821
845
893
913
942
971
1000
1029
1086
1102
1160
TURNS OPEN
4.0
3.0
2.5
2.0
1.0
4.0
3.5
3.0
2.5
2.0
1.5
4.0
3.0
Bold Face Requires Larger 2 HP Motor
A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 2 turns open (3200 cfm @ 0.6 in. ESP). Other speeds require field selection.
ISO/AHRI rating point with standard static sheave and drive at 2 turns open (3200 cfm @ 0.6 in. ESP). Other speeds require field selection.
For applications requiring higher static pressures, contact your local representative.
Performance data does not include drive losses and is based on sea level conditions.
Do not operate in gray region. "na" = information not available at time of printing.
All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12in. wg.
A
B
C
D
E
07/25/07
NLH095 - Blower Performance Data
Belt Drive