ENVISION 7-25 TONS INSTALLATION MANUAL

25

Airflow in CFM with dry coil and clean air filter.

External Static Pressure (in. w.g.)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

1.2

1.4

1.6

1.8

2.0

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

BHP

0.80

0.88

0.96

1.07

1.09

1.11

1.13

1.28

1.36

1.48

1.67

1.86

RPM

707

748

789

830

857

882

907

931

956

1032

1115

1198

TURNS OPEN

5.0

4.0

3.0

2.0

5.0

4.5

4.0

3.5

2.5

1.0

4.5

3.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

BHP

0.90

0.99

1.09

1.16

1.22

1.25

1.27

1.34

1.49

1.63

1.77

1.98

2.08

RPM

707

747

788

830

855

880

905

930

955

1031

1107

1166

1210

TURNS OPEN

5.0

4.0

3.0

2.0

5.0

4.5

4.0

3.5

2.5

1.0

4.0

3.0

2.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

BHP

0.99

1.09

1.20

1.19

1.35

1.38

1.41

1.44

1.47

1.55

1.76

2.06

2.15

2.24

RPM

706

747

787

829

854

879

904

929

954

1004

1070

1137

1180

1224

TURNS OPEN

5.0

4.0

3.0

2.0

5.0

4.5

4.0

3.5

3.0

2.0

4.5

3.5

2.5

2.0

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

BHP

1.05

1.18

1.30

1.32

1.47

1.51

1.54

1.58

1.61

1.85

1.90

2.12

2.22

2.32

2.51

RPM

706

746

787

828

853

878

903

928

953

1001

1044

1103

1134

1184

1233

TURNS OPEN

5.0

4.0

3.0

2.0

5.0

4.5

4.0

3.5

3.0

2.0

5.0

4.0

3.5

2.5

1.5

MTR/SHEAVE

2.0

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

BHP

1.11

1.25

1.39

1.53

1.59

1.63

1.67

1.71

1.75

1.99

2.08

2.16

2.27

2.37

2.64

2.75

RPM

705

756

786

827

853

878

902

927

951

999

1037

1075

1118

1161

1219

1255

TURNS OPEN

5.0

4.0

3.0

2.0

5.0

4.5

4.0

3.5

3.0

2.0

1.0

4.5

3.5

3.0

2.0

1.5

MTR/SHEAVE

2.0

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

3.0

BHP

1.31

1.46

1.61

1.68

1.74

1.79

1.84

1.89

2.13

2.17

2.20

2.43

2.68

2.76

2.84

2.94

RPM

745

786

826

852

877

901

926

950

998

1023

1047

1100

1157

1188

1231

1275

TURNS OPEN

4.0

3.0

2.0

5.0

4.5

4.0

3.5

3.0

2.0

1.0

5.0

4.0

3.0

2.5

1.5

1.0

MTR/SHEAVE

2.0

2.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

3.0

3.0

3.0

3.0

3.0

3.0

BHP

1.52

1.69

1.85

1.88

1.90

1.96

2.02

2.26

2.30

2.34

2.57

2.84

2.91

2.97

3.28

RPM

785

825

851

876

900

925

949

997

1018 1039

1098

1155

1184

1214

1270

TURNS OPEN

3.0

2.0

5.0

4.5

4.0

3.5

3.0

2.0

1.0

5.0

4.5

3.5

2.5

2.0

1.0

A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr

Units factory shipped with standard static sheave and drive at 3.0 turns open (3600 cfm @ 0.9 in. ESP). Other speeds require field selection.

ISO/AHRI rating point with standard static sheave and drive at 2.0 turns open (3600 cfm @ 1.0 in. ESP). Other speeds require field selection.

For applications requiring higher static pressures, contact your local representative.

Performance data does not include drive losses and is based on sea level conditions.

Do not operate in gray region. "na" = information not available at time of printing.

All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.

For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).

Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12in. wg.

3600

3800

4000

4200

Rated CFM

3000

3200

3400

A

B

C

07/23/07

NLH120 - Blower Performance Data

Belt Drive