Electrical Data

Rated

Voltage

Blower

Blower

Total

Min

Max

Voltage

Min/Max

Motor

HP

Unit

Circ

Fuse/

MCC

RLA

LRA

FLA***

***

FLA

Amp

HACR

Horizontal

208-230/60/3

187/253

16.3

10.4

88.0

4.8

1.5

25.7

28.3

35.0

080

460/60/3

414/506

9.0

5.8

38.0

2.4

1.5

13.9

15.4

20.0

575/60/3

518/632

5.9

3.8

36.5

1.9

1.5

9.5

10.4

10.0

208-230/60/3

187/253

16.3

10.4

88.0

6.2

2.0

27.1

29.7

40.0

080**

460/60/3

414/506

9.0

5.8

38.0

3.1

2.0

14.6

16.1

20.0

575/60/3

518/632

5.9

3.8

36.5

2.5

2.0

10.1

11.0

10.0

208-230/60/3

187/253

21.2

13.6

83.1

6.2

2.0

33.3

36.7

50.0

095

460/60/3

414/506

9.5

6.1

41.0

3.1

2.0

15.3

16.8

20.0

575/60/3

518/632

7.8

5.0

34.0

2.5

2.0

12.5

13.7

15.0

208-230/60/3

187/253

21.2

13.6

83.1

9.2

3.0

36.3

39.7

50.0

095**

460/60/3

414/506

9.5

6.1

41.0

4.3

3.0

16.5

18.0

20.0

575/60/3

518/632

7.8

5.0

34.0

3.4

3.0

13.4

14.6

15.0

208-230/60/3

187/253

24.9

15.9

110.0

9.2

3.0

41.1

45.1

60.0

120

460/60/3

414/506

12.1

7.7

52.0

4.3

3.0

19.8

21.7

25.0

575/60/3

518/632

8.9

5.7

38.9

3.4

3.0

14.8

16.2

20.0

Vertical

208-230/60/3

187/253

16.3

10.4

88.0

3.6

1.0

24.5

27.1

35.0

080

460/60/3

414/506

9.0

5.8

38.0

1.8

1.0

13.3

14.8

20.0

575/60/3

518/632

5.9

3.8

36.5

1.5

1.0

9.0

9.9

10.0

208-230/60/3

187/253

16.3

10.4

88.0

4.8

1.5

25.7

28.3

35.0

080**

460/60/3

414/506

9.0

5.8

38.0

2.4

1.5

13.9

15.4

20.0

575/60/3

518/632

5.9

3.8

36.5

1.9

1.5

9.5

10.4

10.0

208-230/60/3

187/253

21.2

13.6

83.1

4.8

1.5

31.9

35.3

45.0

095

460/60/3

414/506

9.5

6.1

41.0

2.4

1.5

14.6

16.1

20.0

575/60/3

518/632

7.8

5.0

34.0

1.9

1.5

11.9

13.1

15.0

208-230/60/3

187/253

21.2

13.6

83.1

6.2

2.0

33.3

36.7

50.0

095**

460/60/3

414/506

9.5

6.1

41.0

3.1

2.0

15.3

16.8

20.0

575/60/3

518/632

7.8

5.0

34.0

2.5

2.0

12.5

13.7

15.0

208-230/60/3

187/253

24.9

15.9

110.0

6.2

2.0

38.1

42.1

50.0

120

460/60/3

414/506

12.1

7.7

52.0

3.1

2.0

18.6

20.5

25.0

575/60/3

518/632

8.9

5.7

38.9

2.5

2.0

13.9

15.3

20.0

208-230/60/3

187/253

24.9

15.9

110.0

9.2

3.0

41.1

45.1

60.0

120**

460/60/3

414/506

12.1

7.7

52.0

4.3

3.0

19.8

21.7

25.0

575/60/3

518/632

8.9

5.7

38.9

3.4

3.0

14.8

16.2

20.0

208-230/60/3

187/253

35.0

22.4

149.0

3.6

1.0

52.0

57.6

80.0

160

460/60/3

414/506

16.5

10.6

75.0

1.8

1.0

24.8

54.0

35.0

575/60/3

518/632

12.0

7.7

54.0

1.5

1.0

18.4

20.3

25.0

208-230/60/3

187/253

35.0

22.4

149.0

4.8

1.5

54.4

60.0

80.0

160**

460/60/3

414/506

16.5

10.6

75.0

2.4

1.5

26.0

28.7

35.0

575/60/3

518/632

12.0

7.7

54.0

1.9

1.5

19.2

21.1

25.0

208-230/60/3

187/253

36.2

23.2

164.0

4.8

1.5

56.0

61.8

80.0

180

460/60/3

414/506

17.5

11.2

75.0

2.4

1.5

27.2

30.0

40.0

575/60/3

518/632

12.3

7.9

54.0

1.9

1.5

19.6

21.6

25.0

208-230/60/3

187/253

36.2

23.2

164.0

6.2

2.0

58.8

64.6

80.0

180**

460/60/3

414/506

17.5

11.2

75.0

3.1

2.0

28.6

31.4

40.0

575/60/3

518/632

12.3

7.9

54.0

2.5

2.0

20.8

22.8

30.0

208-230/60/3

187/253

47.0

30.1

225.0

6.2

2.0

72.6

80.1

110.0

240

460/60/3

414/506

26.0

16.6

114.0

3.1

2.0

39.5

43.6

60.0

575/60/3

518/632

19.0

12.2

80.0

2.5

2.0

29.3

32.4

40.0

208-230/60/3

187/253

47.0

30.1

225.0

9.2

3.0

78.6

86.1

110.0

240**

460/60/3

414/506

26.0

16.6

114.0

4.3

3.0

41.9

46.0

60.0

575/60/3

518/632

19.0

12.2

80.0

3.4

3.0

31.1

34.2

45.0

208-230/60/3

187/253

52.0

33.3

239.0

9.2

3.0

85.0

93.3

125.0

300

460/60/3

414/506

28.0

17.9

125.0

4.3

3.0

44.4

48.9

60.0

575/60/3

518/632

20.0

12.8

80.0

3.4

3.0

32.4

35.6

45.0

*Ratings per each compressor - unit supplied with two

9/10/07

**With optional motor
***Ratings per each blower motor - Vertical models 160-300 supplied with two.

HACR circuit breaker in USA only
All fuses Class RK-5

Compressor*

Model