Da c e, Nlv180 - blower performance data – WaterFurnace Envision (XL) User Manual
Page 19
ENVISION 7-25 TONS INSTALLATION MANUAL
20
Airflow in CFM with dry coil and clean air filter.
External Static Pressure (in. w.g.)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.2
1.4
1.6
1.8
2.0
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
4.0
4.0
BHP
0.61
0.64
0.66
0.68
0.76
0.81
0.87
0.89
0.94
1.05
RPM
581
601
621
663
703
739
774
784
827
867
TURNS OPEN
5.0
4.5
4.0
3.0
2.0
1.5
1.0
0.5
2.0
1.0
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
4.0
4.0
BHP
0.64
0.66
0.71
0.77
0.82
0.85
0.94
0.97
1.04
1.14
RPM
591
611
642
682
712
740
778
795
841
886
TURNS OPEN
4.5
4.0
3.5
2.5
1.5
1.0
0.5
0.0
1.5
0.5
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
4.0
4.0
4.0
BHP
0.65
0.66
0.68
0.75
0.86
0.87
0.88
1.02
1.05
1.14
1.23
RPM
580
600
621
662
701
722
742
782
805
855
905
TURNS OPEN
5.0
4.5
4.0
3.0
2.0
1.5
1.0
0.0
2.5
1.5
0.0
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
5.0
5.0
BHP
0.69
0.70
0.76
0.86
0.92
0.93
1.01
1.08
1.11
1.19
1.30
0.74
0.80
0.85
RPM
590
610
641
681
711
731
761
790
809
850
898
470
480
496
TURNS OPEN
4.5
4.0
3.5
2.5
1.5
1.0
0.5
0.0
3.0
2.5
2.0
1.0
3.0
2.5
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
BHP
0.72
0.73
0.74
0.84
0.96
0.98
0.99
1.13
1.14
1.17
1.23
1.36
1.48
1.59
1.69
RPM
579
600
620
660
700
721
741
780
797
813
845
890
940
960
991
TURNS OPEN
5.0
4.5
4.0
3.0
2.0
1.5
1.0
0.0
3.0
2.5
2.0
1.0
0.0
3.0
2.5
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
5.0
5.0
5.0
BHP
0.76
0.77
0.84
0.95
1.02
1.04
1.12
1.20
1.23
1.27
1.36
1.49
1.58
1.72
1.86
RPM
589
609
640
680
710
730
760
788
808
828
868
914
941
963
991
TURNS OPEN
4.5
4.0
3.5
2.5
1.5
1.0
0.5
0.0
2.5
2.0
1.5
0.5
3.5
2.5
2.0
MTR/SHEAVE
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
3.0
5.0
5.0
5.0
BHP
0.79
0.80
0.82
0.93
1.06
1.08
1.10
1.25
1.26
1.31
1.36
1.49
1.62
1.67
1.85
2.03
RPM
578
599
619
659
699
719
739
778
795
819
843
890
937
942
967
991
TURNS OPEN
5.0
4.5
4.0
3.0
2.0
1.5
1.0
0.0
3.0
2.5
2.0
1.0
0.0
3.0
2.5
2.0
Bold Face Requires Larger 2.0 HP Motor
A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 3 turns open (5600 cfm @ 0.6 in. ESP). Other speeds require field selection.
ISO/AHRI rating point with standard static sheave and drive at 1.5 turns open (5600 cfm @ 0.7 in. ESP). Other speeds require field selection.
For applications requiring higher static pressures, contact your local representative.
Performance data does not include drive losses and is based on sea level conditions.
Do not operate in gray region. "na" = information not available at time of printing.
All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12 in. wg.
BHP is given for each blower. Multiply BHP x 2 for unit BHP.
7/25/07
5800
6000
6200
6400
Rated CFM
5200
5400
5600
D
A
C
E
NLV180 - Blower Performance Data
Belt Drive