Ab e, Nlv160 - blower performance data – WaterFurnace Envision (XL) User Manual
Page 18
ENVISION 7-25 TONS INSTALLATION MANUAL
19
Airflow in CFM with dry coil and clean air filter.
External Static Pressure (in. w.g.)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
MTR/SHEAVE
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
BHP
0.29
0.33
0.38
0.37
0.45
0.47
0.50
0.54
0.58
0.64
0.69
0.71
0.73
0.84
0.95
1.05
RPM
437
478
518
539
586
617
647
677
707
736
765
775
809
843
876
909
TURNS OPEN
4.0
3.0
2.0
1.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
3.5
3.0
2.5
2.0
1.5
MTR/SHEAVE
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
BHP
0.33
0.38
0.41
0.44
0.50
0.53
0.57
0.61
0.66
0.71
0.75
0.77
0.84
0.95
1.04
1.13
RPM
457
498
528
562
601
631
661
691
720
750
770
791
825
858
892
925
TURNS OPEN
3.5
2.5
1.5
0.5
4.5
4.0
3.5
3.0
2.5
2.0
1.0
3.0
2.5
2.0
1.5
1.0
MTR/SHEAVE
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
5.0
BHP
0.38
0.44
0.43
0.52
0.56
0.59
0.63
0.68
0.73
0.78
0.81
0.83
0.94
1.05
1.13
1.20
RPM
477
517
538
585
615
645
675
704
734
763
774
807
841
874
907
940
TURNS OPEN
3.0
2.0
1.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
3.5
3.0
2.5
2.0
1.5
1.0
MTR/SHEAVE
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
5.0
BHP
0.44
0.47
0.51
0.58
0.62
0.66
0.70
0.75
0.81
0.85
0.87
0.94
1.05
1.15
1.22
0.60
RPM
497
527
561
599
629
659
688
718
747
768
790
823
856
889
923
470
TURNS OPEN
2.5
1.5
1.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
3.0
2.5
2.0
1.5
1.0
0.5
MTR/SHEAVE
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
5.0
BHP
0.49
0.50
0.59
0.63
0.67
0.72
0.77
0.83
0.89
0.91
0.94
1.05
1.17
1.24
1.32
RPM
516
537
584
614
643
673
702
732
761
772
806
839
871
905
938
TURNS OPEN
2.0
1.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
3.5
3.0
2.5
2.0
1.5
1.0
MTR/SHEAVE
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
5.0
BHP
0.53
0.58
0.65
0.69
0.74
0.79
0.85
0.91
0.95
0.98
1.05
1.17
1.27
1.34
0.66
RPM
526
560
598
628
657
686
716
745
766
788
821
854
887
920
469
TURNS OPEN
1.5
1.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
3.0
2.5
2.0
1.5
1.0
0.5
MTR/SHEAVE
2.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
5.0
5.0
5.0
5.0
5.0
5.0
BHP
0.56
0.66
0.71
0.75
0.81
0.86
0.92
0.99
1.02
1.05
1.17
1.29
1.37
1.44
RPM
536
582
612
642
671
700
729
758
770
804
837
869
903
936
TURNS OPEN
1.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
3.5
3.0
2.5
2.0
1.5
1.0
Bold Face Requires Larger 1.5 HP Motor
A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 3 turns open (5000 cfm @ 0.6 in. ESP). Other speeds require field selection.
ISO/AHRI rating point with standard static sheave and drive at 2.0 turns open (5000 cfm @ 0.7 in. ESP). Other speeds require field selection.
For applications requiring higher static pressures, contact your local representative.
Performance data does not include drive losses and is based on sea level conditions.
Do not operate in gray region. "na" = information not available at time of printing.
All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12 in. wg.
BHP is given for each blower. Multiply BHP x 2 for unit BHP.
7/25/07
5000
5200
5400
5600
Rated CFM
4400
4600
4800
A
B
E
NLV160 - Blower Performance Data
Belt Drive