Ab c, Nlv300 - blower performance data – WaterFurnace Envision (XL) User Manual
Page 21
ENVISION 7-25 TONS INSTALLATION MANUAL
22
Airflow in CFM with dry coil and clean air filter.
External Static Pressure (in. w.g.)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.2
1.4
1.6
1.8
2.0
MTR/SHEAVE
2.0
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
BHP
1.46
1.49
1.77
1.94
2.11
2.29
2.32
2.39
2.65
2.72
2.80
2.36
RPM
677
696
745
778
810
841
858
878
912
932
951
994
TURNS OPEN
5.0
4.0
3.0
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
MTR/SHEAVE
2.0
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
BHP
1.55
1.70
1.86
2.03
2.21
2.39
2.42
2.50
2.75
2.83
2.91
2.63
2.61
RPM
674
708
742
774
806
837
853
873
907
926
945
981
1010
TURNS OPEN
5.0
4.0
3.0
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
4.0
MTR/SHEAVE
2.0
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
BHP
1.63
1.79
1.96
2.13
2.31
2.49
2.52
2.60
2.85
2.93
3.01
2.87
2.87
2.86
RPM
671
705
738
771
802
833
849
869
903
922
940
969
997
1025
TURNS OPEN
5.0
4.0
3.0
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
4.0
3.5
MTR/SHEAVE
2.0
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
BHP
1.72
1.88
2.04
2.22
2.40
2.58
2.62
2.70
2.95
3.03
3.11
3.09
3.10
3.11
RPM
668
702
735
767
799
829
845
864
898
917
935
959
985
1012
TURNS OPEN
5.0
4.0
3.0
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
4.0
3.5
MTR/SHEAVE
2.0
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
BHP
1.96
2.13
2.31
2.49
2.68
2.71
2.79
3.05
3.13
3.21
3.29
3.31
3.33
RPM
699
732
764
795
825
841
860
894
912
931
949
975
1001
TURNS OPEN
4.0
3.0
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
4.0
3.5
MTR/SHEAVE
2.0
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
BHP
2.21
2.39
2.58
2.77
2.81
2.89
3.13
3.22
3.31
3.39
3.51
3.54
3.56
RPM
729
761
792
821
837
856
890
908
926
944
965
990
1016
TURNS OPEN
3.0
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
4.0
3.5
3.0
MTR/SHEAVE
2.0
2.0
1.0
1.0
1.0
1.0
1.0
1.0
3.0
3.0
3.0
3.0
BHP
2.48
2.66
2.85
2.90
2.98
3.23
3.32
3.40
3.48
3.61
3.73
3.76
RPM
758
788
818
833
852
885
904
922
939
960
980
1005
TURNS OPEN
2.0
1.0
4.0
3.5
3.0
2.0
1.5
1.0
4.5
4.0
3.5
3.0
A=Std Static/Std Mtr;B=Low Static/Std. Mtr;C=High Static/Std. Mtr;D=Std Static/Large Mtr;E=High Static/Large Mtr
Units factory shipped with standard static sheave and drive at 3.0 turns open (9500 cfm @ 0.7 in. ESP). Other speeds require field selection.
ISO/AHRI rating point with standard static sheave and drive at 3.0 turns open (9500 cfm @ 0.7 in. ESP). Other speeds require field selection.
For applications requiring higher static pressures, contact your local representative.
Performance data does not include drive losses and is based on sea level conditions.
Do not operate in gray region. "na" = information not available at time of printing.
All airflow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]).
Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, and 400 fpm by 0.12 in. wg.
BHP is given for each blower. Multiply BHP x 2 for unit BHP.
7/25/07
9600
10000
10400
10800
Rated CFM
8400
8800
9200
A
B
C
NLV300 - Blower Performance Data
Belt Drive