Optional fx10 microprocessor control - bacnet – WaterFurnace Envision (XL) User Manual
Page 34

ENVISION 7-25 TONS INSTALLATION MANUAL
35
Object Type
Type Enumeration
Instance
Name
Enumeration
Analog Value
2
1
Present_Value
85
WFI##########.Occupied Cool.Present_Value
Occupied Cooling Setpoint Input (Read/Write)
Standby Cooling Setpoint Input (Read/Write)
Analog Value
2
3
Present_Value
85
WFI##########.Unoccupied Cool.Present_Value
Unoccupied Cooling Setpoint Input (Read/Write)
Analog Value
2
2
Present_Value
85
WFI##########.Occupied Heat.Present_Value
Occupied Heating Setpoint Input (Read/Write)
Standby Heating Setpoint Input (Read/Write)
Analog Value
2
4
Present_Value
85
WFI##########.Unoccupied Heat.Present_Value
Unoccupied Heating Setpoint Input (Read/Write)
Analog Value
2
7
Present_Value
85
WFI##########.Min Clg Setpt.Present_Value
Minimum Cooling Setpoint Input (Read/Write)
Analog Value
2
6
Present_Value
85
WFI##########.Max Htg Setpt.Present_Value
Maximum Heating Setpoint Input (Read/Write)
Analog Input
0
1
Present_Value
85
WFI##########.Space Temp.Present_Value
Space or Zone Temperature Value (Read Only)
Analog Input
0
2
Present_Value
85
WFI##########.Discharge Air Temp.Present_Value
Discharge Air Temp Field Supplied Only (Read Only)
Analog Input
0
5
Present_Value
85
WFI##########.Effective Clg Setpt.Present_Value
Effective Cooling Setpoint Value (Read Only)
Analog Input
0
6
Present_Value
85
WFI##########.Effective Htg Setpt.Present_Value
Effective Heating Setpoint Value (Read Only)
Analog Output
1
2
Present_Value
85
WFI##########.Space temp Ovrd.Present_Value
Space or Zone Temperature Value Override(Write)
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
1st Stage Compressor Heating Output (Read Only)
1st Stage Compressor Cooling Output (Read Only)
Fan Output (Read Only)
Multistate Input
13
2
Present_Value
85
WFI##########.Mode.Present_Value
Unit Mode of Operation (Read Only)
Unit Alarm mode (Read Only)
Heating/Cooling Prop Band Input (Read/Write)
Analog Value
2
9
Present_Value
85
WFI##########.Remote Setpt Min.Present_Value
Warm/Cool Adjust Min (Read/Write)
Analog Value
2
8
Present_Value
85
WFI##########.Remote Setpt Max.Present_Value
Warm/Cool Adjust Max (Read/Write)
Analog Value
2
10
Present_Value
85
WFI##########.Zone Temp Offset.Present_Value
Space or Zone Temperature Sensor Calibration Input (Read/Write)
Analog Output
1
1
Present_Value
85
WFI##########.Common Setpoint.Present_Value
General Setpoint Input (Read/Write)
Analog Input
0
3
Present_Value
85
WFI##########.Freez Temp 1.Present_Value
Heating Freeze Protection Temperature 1 Value (Read Only)
Analog Input
0
3
Present_Value
85
WFI##########.Freez Temp 2.Present_Value
Heating Freeze Protection Temperature 2 Value (Read Only)
Analog Input
0
8
Present_Value
85
WFI##########.nvoAlarms.Present_Value
Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge Pressure
alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze protection alarm, 8=Faulty Freeze
Sensor alarm, 9=Loss of Charge] (Read Only)
Analog Input
0
9
Present_Value
85
WFI##########.Economizer Temp.Present_Value
Main Loop Temp for Economizer Control (Read Only)
Analog Input
2
5
Present_Value
85
WFI##########.Economizer Setpt.Present_Value
Setpoint for Economizer (Read/Write)
Analog Value
2
11
Present_Value
85
WFI##########.EconomizerTempOffset.Present_Value
Economizer Temperature Sensor Calibration Input (Read/Write)
Analog Input
0
7
Present_Value
85
WFI##########.Freez Temp Limit.Present_Value
Heating Freeze Protection Temperature Setpoint Value (Read Only)
Compressor Stage Lead/Lag hour setting (Read/Write)
Multistate Input
13
1
Present_Value
85
WFI##########.Effective Occupancy.Present_Value
Effective Occupancy State (Read Only)
Multistate Output
14
1
Present_Value
85
WFI##########.Occupancy Command.Present_Value
Occupancy Override Command Input (Read/Write)
Multistate Output
14
6
Present_Value
85
WFI##########.Emergency Override.Present_Value
Emergency Override Input (Read/Write)
Binary Input
3
1
Present_Value
85
WFI##########.Fan Cmd Status.Present_Value
Fan Output Status (Read Only)
Accessory 2 Output Status (Read Only)
Accessory 1 Output Status (Read Only)
Alarm Output Status (Read Only)
Multistate Output
14
7
Present_Value
85
WFI##########.Alarm Reset.Present_Value
Alarm Reset Input (Read/Write)
Multistate Output
14
2
Present_Value
85
WFI##########.Fan Command (G).Present_Value
Network equivelant of a thermostatic 'G' call. (Write)
Multistate Output
14
3
Present_Value
85
WFI##########.Comp1 Command (Y1).Present_Value
Network equivelant of a thermostatic 'Y1' call. (Write)
Multistate Output
14
4
Present_Value
85
WFI##########.Comp2 Command (Y2).Present_Value
Network equivelant of a thermostatic 'Y2' call. (Write)
Multistate Output
14
5
Present_Value
85
WFI##########.Rev Vlv Cmd (O).Present_Value
Network equivelant of a thermostatic 'O' call. (Write)
Binary Input
3
2
Present_Value
85
WFI##########.Comp1 Cmd Status.Present_Value
Compressor 1 Command Status (Read Only)
Binary Input
3
4
Present_Value
85
WFI##########.Reversing Valve.Present_Value
Reversing Valve Output Status (Read Only)
Occupancy Supervisory Scheduler Command Input (Read/Write)
Binary Input
3
3
Present_Value
85
WFI##########.Comp2 Cmd Status.Present_Value
Compressor 2 Command Status (Read Only)
Compressor Stage Lead/Lag Enable/Disable (Read/Write)
Multistate Value
19
1
Present_Value
85
WFI##########.Economizer Ena/Dis.Present_Value
Water Side Economizer Enable/Disable (Read/Write)
Multistate Input
13
3
Present_Value
85
WFI##########.Compressor/Fan Prove.Present_Value
Compressor/Fan Proving Switch Status (Read Only)
Multistate Output
14
8
Present_Value
85
WFI##########.Emergency Heat BO5.Present_Value
Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)
Binary Input
3
5
Present_Value
85
WFI##########.BO5 ElecHeat.Present_Value
Value Output for BO5 used for Emg Heat (Read Only)
Multistate Output
14
9
Present_Value
85
WFI##########.BO9.Present_Value
Command for output BO9(Read/Write)
Binary Input
3
9
Present_Value
85
WFI##########.BO9 Output.Present_Value
Value output for BO9 (Read Only)
Point Description
Object Identifier
Property
BACnet
Full Reference
Optional FX10 Microprocessor Control - BACnet