beautypg.com

Module features – Spectrum Controls 140 EHC 204 00sc User Manual

Page 9

background image

Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc

10

The module’s flow meter mode is compatible with a variable reluctance AC input, which counts AC zero crossing

signals from 50 mV to 75V AC peak.

Count input modes include uni-directional, bi-directional and quadrature. Bi-directional and quadrature inputs

require the use of two inputs, with up to four counters of this type being supported.

The module accepts +5 to +45 V gating (enable) pulses for standard meter proving applications. To

accommodate these pulses, the module uses a pulse-to-enable converter circuit that can be enabled and disabled

with software. Note that this module does not perform pulse interpolation for meter proving.

The module also has external inhibit/trigger lines using a 5V discrete pulse to regulate activity.

Module Features

The Quantum counter module features:

Eight input channels

Support for four quadrature encoders

Eight external enable inputs

Input voltage ranges: AC (50 mV to 75V peak), 5VDC, 12VDC, 24VDC

Eight 24V gating (enable) pulses for meter proving

Input filter frequency 50 kHz max., AC or DC

Maximum count value 65 K or 16 M

Programmable scaling, K, M, and R factors

Channel update time 4 ms/channel

Rate output

Counter logic level state

Programmable counter functions: start, stop, reset, preset, max limit

Programmable counter alarm flags and zero flags in internal counter and rate operating modes

Two software-selectable filters: 30 or 50 kHz digital, 15 kHz analog

Channel-to-backplane isolation 1000VDC

Channel-to-channel isolation 0 V