Spectrum Controls 140 EHC 204 00sc User Manual
Page 39
Quantum Series 140 EHC 204 00sc 140 EHC 208 00sc
40
Bit Settings for 3X+0 Registers
The 3X+0 registers contain data, scaling and status information for channels 1 through 8. You
can only set 3X register bits using ladder logic. This section describes the layout for the registers
and defines the bits. Ladder logic examples are provided in chapter 4, “Programming.”
Table 3-7 3X+0 Register Bit Settings
Function
1
2
3
4
5
6
7
8
9
10
11 12 13 14
15 16
Bank/Data Format
Bank 1/ LSW
0
0
Select Echo
Bank 2/ MSW
0
1
Bank 3/Rate
1
0
Bank 4/ Status
1
1
Data Delivery Echo Comprehensive
0
Speed
1
Multiplexing
Manual
0
Control Echo
Autosequence
1
Parameter Definition Preset
0
0 0
Echo
Count Limit
0
0 1
(for scale/limit word) Rate Limit
0
1 0
M factor
0
1 1
K Factor
1
0 0
R factor
1
0 1
Not Used
X
Channel Number
Channel 1
0
0
0
Echo
Channel 2
0
0
1
(for scale/limit word) Channel 3
0
1
0
Channel 4
0
1
1
Channel 5*
1
0
0
Channel 6*
1
0
1
Channel 7*
1
1
0
Channel 8*
1
1
1
Not Used
X
Configuration Error No Error
0
Error
1
System Error
No Error
0
Error
1
Program
Do Not Program
0
EEPROM Echo
Program
1
Enable Scale
Disable
0
/Limit Word
Enable
1
Echo
All fields in the above table are echoes of what is in the 4X+0 register except configuration error and system error. Refer
to the section Configuration Word (4X+0 Register) for more details. Configuration error indicates an erroneous configu-
ration has been input for at least one input channel. A system error indicates a problem with either the module or with a
module input.