beautypg.com

Setting zoom registers using concept – Spectrum Controls 140 EHC 204 00sc User Manual

Page 26

background image

Counter / Flow Meter Input Module

27

Setting Zoom Registers Using Concept

The next procedure describes how to enable the zoom registers and make configuration settings in Concept.

Refer to “

Zoom Register Layout

.

”

1. Ensure that the Concept software has been updated from the installation disk as described in “

Setting

Up Concept

.”

2. Start the Concept Modconnect tool (Modconf.exe).

3. From Modconnect, open the file SPECTRUM.MDC.

4. Select the Quantum counter module, or click Add All.

5. Save your changes and exit Modconnect to update the Concept database. The changes are permanent

unless you later undo the changes using Modconnect, or perform a new Concept software installation.

6. In Concept, create a new project.

7. Enter the starting 3X register address (InRef). Nine registers are automatically allocated.

8. Enter the starting 4X register address (OutRef). 6/10 registers are allocated. (4ch - 6 / 8ch - 10)

9. Select the Configurator tool from the project pulldown menu.

10. Choose Configure, then click I/O Map to open the I/O map editor.

11. In the I/O map screen, type the number for the correct “drop” and click Edit.

12. From the list presented, select the Spectrum Controls catalog number of the module.

13. Click the button in the module select column for the appropriate rack slot.

14. The next screen represents your module. Click the parameters button.

15. Insert hexadecimal values for registers 1-9 (1-5 for the 4-ch module) to fully configure the module if

you are not using the SCIOCFG utility program.

This manual is related to the following products: