Counter / Flow Meter Input Module

29

Zoom Register Layout

The following table shows the layout for each of the zoom registers. The 8 channel module uses this layout for

the first eight registers. The four channel uses the first 4 zoom registers. (The nineth - 8 channel or 5th - channel

zoom register specifies the Bank Switch Period in the Autosequence Mode.) , with bit 1 the MSB and bit 16 the

LSB.

Table 3-3 Bit Settings for Zoom Registers

Function

1

2

3

4

5

6

7

8

9

10

11 12 13 14

15 16

Input range*

5V **

0

0

12V

0

1

24V

1

0

AC

1

1

Count mode*

Unidirectional **

0

0

Bidirectional

0

1

Quad. 1X

1

0

Quad. 4X

1

1

30kHz filter

Disabled **

0

Enabled

1

15 kHz filter

Disabled **

0

Enabled

1

Count size

65K **

0

16M

1

Rate Scale

1.0Hz

0

0.1Hz

1

Unused

X

X

X

X

X

X

X

X

* Channel Pairs (1-2, 3-4, 5-6, 7-8) must be configured the same to operate properly.
** Default Settings

Input Range, Bits 15 and 16

These bits select one of the four available input ranges: 5V, 12V, 24V and AC. Select the range that is closest to

the maximum amplitude of your device signal. For example: If your flow meter has a peak signal amplitude of

20 volts, select the 24V input range. Each range selection determines the counter trip level. Matching the input

range to your signal amplitude will miximize false counting.

NOTE: Allow at least one scan time for input range information to be updated at the PLC.

NOTE: Channel pairs (1-2, 3-4, 5-6, 7-8) must be configured with identical input ranges to function properly.

Count Mode, Bits 13 and 14

The count mode bits select the type of input operation. Possible types are:

Unidirectional

Bidirectional

Quadrature 1X

Quadrature 4X