Module not recognized by rack (modsoft) – Spectrum Controls 140 EHC 204 00sc User Manual
Page 64
![background image](/manuals/742156/64/background.png)
Counter / Flow Meter Input Module
65
Corrective Action
If necessary, install a pull-down resistor between the channel input and channel common or a pull-up resistor
to a positive voltage source.
Module Not Recognized by Rack (ModSoft)
Possible Causes
•
Module not correctly installed.
•
Module runtime files not correctly installed.
Corrective Action
1. Reinstall the module in the rack. See chapter 2, “Installation and Wiring.”
2. Check the I/O map screen in ModSoft to see if the problem still exists.
3. If the module name is still marked with an asterisk (indicating a health status problem), select the
module name using the Shift+? key.
4. If the module is not listed at all, reinstall the ModSoft runtime files. See software installation
instructions in chapter 3, “Module Configuration.”