The flow meter mode is compatible with a variable reluctance AC input, which counts AC zero crossing signals
from 50 mV to 75V AC peak.
The module accepts +5 to +45 V gating (enable) pulses for standard meter proving applications. This module
does perform pulse interpolation for meter proving allowing short run prover verification.
The module also has external inhibit/trigger lines using a 5V discrete pulse to regulate activity.
Module Features
Module Features
Module Features
Module Features
Module Features
The Quantum counter module features:
•
Four input channels
•
Four redundant input channels for pulse fidelity checking
(API Level B, phase, sequence, count, frequency monitoring)
•
Four external enable inputs
•
Double Chronometry Pulse Interpolation which allows 4 decimal places of resolution.
•
Four gating (enable) pulses for meter proving
•
Input filter frequency 50 kHz max., AC or DC
•
Maximum count value 65 K or 16 M
•
Programmable scaling, K, M, and R factors
•
Channel update time 1 ms/channel
•
Rate output with programmable timeout allowing low frequency measurement
•
Meter logic level state
•
Programmable counter alarm flags and rate operating modes
•
Two software-selectable filters: 30 or 50 kHz digital, 15 kHz analog
•
Channel-to-backplane isolation 1000VDC
•
Channel-to-channel isolation 0 V