Meter Input Modes

Meter Input Modes

Meter Input Modes

Meter Input Modes

Meter Input Modes

The flow meter mode is compatible with a variable reluctance AC input, which counts AC zero crossing signals
from 50 mV to 75V AC peak.

The module accepts +5 to +45 V gating (enable) pulses for standard meter proving applications. This module
does perform pulse interpolation for meter proving allowing short run prover verification.

The module also has external inhibit/trigger lines using a 5V discrete pulse to regulate activity.

Module Features

Module Features

Module Features

Module Features

Module Features

The Quantum counter module features:

Four input channels

Four redundant input channels for pulse fidelity checking

(API Level B, phase, sequence, count, frequency monitoring)

Four external enable inputs

Double Chronometry Pulse Interpolation which allows 4 decimal places of resolution.

Four gating (enable) pulses for meter proving

Input filter frequency 50 kHz max., AC or DC

Maximum count value 65 K or 16 M

Programmable scaling, K, M, and R factors

Channel update time 1 ms/channel

Rate output with programmable timeout allowing low frequency measurement

Meter logic level state

Programmable counter alarm flags and rate operating modes

Two software-selectable filters: 30 or 50 kHz digital, 15 kHz analog

Channel-to-backplane isolation 1000VDC

Channel-to-channel isolation 0 V