Spectrum Controls 140 MPM 204 00sc User Manual
Page 21

Meter Proving Module
23
Specification
Specification
Specification
Specification
Specification
V
V
V
V
Value
alue
alue
alue
alue
Wire Type
Stranded, Cu-90°C (194°F)
Wire Size
16 to 22 AWG
Terminal Screw Torque
0.68 Nm (6 in-lb)
Retaining Screw Torque
0.46 Nm (4.1 in-lb)
To wire the terminal block:
1.
1.
1.
1.
1. Determine the length of cable you need to connect a channel to its field device. Remember to include
additional cable to route the drain wire and foil shield to their ground points.
2.
2.
2.
2.
2. If you need to remove the terminal block cover, insert a screwdriver into one of the square wiring holes,
and gently pry the cover off. Be sure to replace the cover before proceeding.
3.
3.
3.
3.
3. Loosen the terminal screw to be wired.
4.
4.
4.
4.
4. Route the wire under the terminal pressure plate.
5.
5.
5.
5.
5. Connect only one end of the shield to the module. You can use the bare wire or a spade lug. The
terminals accept a 6.35 mm (0.25 in.) spade lug.
6.
6.
6.
6.
6. Tighten the terminal screw, making sure the pressure plate secures the wire.
7.
7.
7.
7.
7. A removable write-on label (ID tag) is provided with the terminal block. Remove the label from the
door, mark the identification of each terminal with permanent ink, and slide the label back into the door.
The ID tag is visible when the module door is closed.
W
W
W
W
Wiring the Module for Inputs
iring the Module for Inputs
iring the Module for Inputs
iring the Module for Inputs
iring the Module for Inputs
After the terminal block is wired, use the procedure in this section to connect the inputs to the terminal block.
To ensure proper operation and high immunity to electrical noise, always use Belden 8761 shielded, twisted-pair
wire, or equivalent.
CAUTION -
CAUTION -
CAUTION -
CAUTION -
CAUTION - To prevent shock hazard, take care when wiring the module to analog signal
sources. Before wiring, disconnect power from the system power supply and from any other
source.
1. At each end of the first cable, strip some casing to expose the individual wires.
2. On each end of the cable, separate the wires and trim the signal wires to 5.08 cm (2 in.) lengths. Strip about 4.76
mm (.18 in.) of insulation to expose the end of each wire. Be sure to not cut the wires too short.
CAUTION -
CAUTION -
CAUTION -
CAUTION -
CAUTION - Be careful when stripping wires. Wire fragments that fall into a module could
cause damage at startup