Appendix D: Configuring the IT6I for CompactLogix Controllers in RSLogix 5000
D-3
User’s Manual Pub. 0300244-01 Rev. A
First, select the Comm Format (“Input Data – INT” for the 1769sc-IT6I), then fill in the
name field. For this example, “IT6I” is used to help identify the module type in the
Controller Organizer. The Description field is optional and may be used to provide more
details concerning this I/O module in your application.
The slot number must be selected next, although it will begin with the first available slot
number, 1, and increments automatically for each subsequent Generic Profile you
configure. For this example, the 1769sc-IT6I Isolated Thermocouple module is located
in slot 1.
The Comm Format, Assembly Instance and Size values are listed in the following table
for the 1769sc-IT6I Thermocouple module:
Table D-1 (Generic Profile Settings)
1769 I/O
Module
Comm.
Format
Parameter Assembly
Instance
Size
(16-Bit)
IT6I
Input Data - INT Input
101
8
Output 104 0
Config. 102
16
Enter the Assembly Instance numbers and their associated sizes for the 1769sc-IT6I
module into the Generic Profile. When complete, the Generic Profile for a 1769sc-IT6I
module should look like the following: