4.2.4

Selecting Data Formats (Bits 12 through 14)

This selection configures channels 0 through 5 to present analog data in any of the
following formats:

Raw/Proportional Data

Engineering Units x 1

Engineering Units x 10

Scaled for PID

Percent Range

Table 4-3 (Channel Data Word Format)

Input

Type

Data Format

Engineering Units x 10

Engineering Units x 1

Scaled

For

PID

Proportional

Counts

˚ Celsius

˚ Fahrenheit

˚ Celsius

˚ Fahrenheit

J

-210 to 1200

-346 to 2192

-2100 to 12000

-3460 to 21920

0 to 16383

-32767 to 32767

K

-270 to 1370

-454 to 2498

-2700 to 13700

-4540 to 24980

0 to 16383

-32767 to 32767

T

-270 to 400

-454 to 752

-2700 to 4000

-4540 to 7520

0 to 16383

-32767 to 32767

E

-270 to 1000

-454 to 1832

-2700 to 10000

-4540 to 18320

0 to 16383

-32767 to 32767

R

0 to 1768

32 to 3214

0 to 17680

320 to 32144

0 to 16383

-32767 to 32767

S

0 to 1768

32 to 3214

0 to 17680

320 to 32144

0 to 16383

-32767 to 32767

B

300 to 1820

572 to 3308

3000 to 18200

5720 to 32767

5

0 to 16383

-32767 to 32767

N

-210 to 1300

-346 to 2372

-2100 to 13000

-3460 to 23720

0 to 16383

-32767 to 32767

C

0 to 2315

32 to 4199

0 to 23150

320 to 32767

5

0 to 16383

-32767 to 32767

L

-200 to 900

-328 to 1652

-2000 to 9000

-3280 to 16520

0 to 16383

-32767 to 32727

+/- 50 mV

-500 to 500

2

-500

to

500

2

-5000

to

5000

2

-5000

to

5000

6

0 to 16383

-32767 to 32767

+/- 100 mV

-1000 to 1000

2

-1000 to 1000

2

-10000 to 10000

2

-10000 to 10000

6

0 to 16383

-32767 to 32767

Note: The engineering units data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional counts, scaled-
for-PID and percent of full-scale data formats may yield the highest effective
resolutions, but may also require that you convert channel data to real engineering
units in your control program.

Raw/Proportional Data

The value presented to the controller is proportional to the selected input and scaled into
the maximum data range allowed by the bit resolution of the A/D converter and filter

5

Type B and C thermocouples cannot be represented in engineering units x 1 (°F) above 3276.7°F. Software treats

it as an over range error.

6

When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F

selection.