Spectrum Controls 1769sc-HART Modules User Manual

Page 70

background image

Compact IO™ Isolated HART Analog Output Module

User’s Manual 0300217-03 Rev. A

7-4

Figure 7-3 (Auto Acquisition Flow)

The data that is collected from the process described in Figure 7-4 (Auto Acquisition
Flow) is buffered to the module RAM memory. Since the amount of data returned from
the auto-acquisition process is extensive, the data is multiplexed into five separate
packets and for each individual channel. The multiplexed data can be read from a 40 byte
array which is located in the OF4IH0Input.HartData tag. The multiplexed data is
demultiplexed using ladder and stored in five different arrays which are structured using
packets zero through four. The packets are defined as “user defined data types” and can
be seen in Table 7-1 through Table 7-5.

Start

Channel

Switch

Initializ

ed for

HART?

Connect to field

device

Read device

codes

Read extended

status

Read ASCII

messages

Read PVU and

PVL

Read 4 dynamic

variables

Read slot variables

if enabled

No

Yes