Spectrum Controls 1769sc-HART Modules User Manual
Page 168
Compact IO™ Isolated HART Analog Output Module
User’s Manual 0300217-03 Rev. A
A-2
Environmental
Specifications
Shock & Vibration (op)
Class III
Shock Unpackaged (op)
Class III, Cat. I
Operating Temperature
0 to 60 Degree C
1
Storage Temperature
-40 to 85 Degree C
Humidity/Pressure
5 to 95% RH (non cond.)
Regulatory
Compliance
UL 508
ANSI/ISA 12.12.01
UL-C Class 1, Div2 Group A, B, C, D (CSA Equiv.)
CE compliance to EN 61010-1 and EN 61131-2, EN55011, EN50082-2, and
EN61000-6-2
EN60079-0, EN60079-15 ATEX
Conditions of safe use:
Provision shall be made to prevent the rated voltage being exceeded by the
transient disturbances of more than 140% of the peak rated voltage.
The system shall be mounted in an ATEX certified enclosure with a minimum
ingress protection rating of at least IP54 as defined in EN60529 and used in an
environment of not more than pollution degree 2.
The enclosure must have a door or cover accessible only by the use of a tool.
1
Avoid installing the module adjacent to modules with heat dissipation greater than 4 Watts when the ambient
temperature is in excess of 55°C. See Section 3.3.4 Selecting a Location, for more details.
0C < Ta < 60C
DEMKO 11 ATEX 1103437X
Ex nA IIC T4 Gc
II 3G