I:e.0/2 – Spectrum Controls 1769sc-HART Modules User Manual
Page 44
Compact IO™ Isolated HART Analog Output Module
User’s Manual 0300217-03 Rev. A
5-2
For example, to obtain the general status for channel 2 of the module located in slot e, use
address I:e.0/2.
Figure 5-2 (Address Example)
NOTE: The end cap does not use a slot address.
Section 5.2
Configuring
the 1769sc-OF4IH
in a MicroLogix
1500 System
This example takes you through configuring your 1769sc-OF4IH isolated HART analog
output module with RSLogix 500 programming software, assumes your module is
installed as expansion I/O in a MicroLogix 1500 system, and that RSLinx™ is properly
configured and a communications link has been established between the MicroLogix
processor and RSLogix 500.
It is recommended that a 1764-LRP series C processor with firmware
version 5 or higher be used. The LRP processor supports floating
point files, which is required to read floating point data from the
OF4IH.
Start RSLogix and create a MicroLogix 1500 application. The following screen appears:
Slot
Word
Bit
Input File Type
Element
Delimiter
Word
Delimiter
Bit
Delimiter
I:e.0/2
!