2 extended error information field – Spectrum Controls 1769sc-HART Modules User Manual
Page 164
Compact IO™ Isolated HART Analog Output Module
User’s Manual 0300217-03 Rev. A
9-4
Table 9-3 (Module Error Types)
Er r or Type
M odule Er r or
Fie ld V alue Bits
11 thr ough 9
(binar y)
De s cr iption
No errors
000
No error is present. The extended error f ield holds no
additional inf ormation.
Hardw are
Errors
001
General and s pec if ic hardw are error c odes are
spec if ied in the ex tended error inf ormation f ield.
Conf iguration
Errors
010
Module-spec if ic error codes are indicated in the
ex tended error f ield. Thes e error codes c orrespond to
options that you c an c hange direc tly . For ex ample, the
input range or input f ilter s elec tion.
9.6.2 Extended Error Information Field
Check the extended error information field when a non-zero value is present in the
module error field. Depending upon the value in the module error field, the extended
error information field can contain error codes that are module-specific or common to all
1769 analog modules.
Note: If no errors are present in the module error field, the extended error
information field is set to zero.
Hardware Errors
General or module-specific hardware errors are indicated by module error code 001. See
Table 9-4 (Extended Fault Codes).
Configuration Errors
If you set the fields in the configuration file to invalid or unsupported values, the module
generates a critical error.
Table 9-4 (Extended Fault Codes) lists the possible module-specific configuration error