Spectrum Controls 1769sc-HART Modules User Manual
Page 47
Chapter 5: Configuring the OF4IH for A MicroLogix 1500 Using RSLogix 500
User’s Manual 0300217-03 Rev. A
5-5
Figure 5-7
When using the read IO configuration feature in RSLogix, you need
to manually enter 42 into the “extra data length” field.
To configure the module select the Generic Extra Data Configuration tab. Enter the
decimal equivalent of each configuration word. There are a total of 42 words that need to
be configured altogether. The module default settings are used if all the configuration
words are left at zero.
Figure 5-8
NOTE: For a complete description of each of these parameters and the choices
available for each of them, refer to Chapter 6.
!
Attention