beautypg.com

Spectrum Controls 1769sc-HART Modules User Manual

Page 61

background image

Chapter 6: Module Data, Status, and Configuration

User’s Manual 0300217-03 Rev. A

6-9

Note: The range of this value is defined by the data format selected for the channel.

6.3.16 Low Clamp Value (Words 4, 12, 20, 28)

The low clamp value determines the minimum analog signal that will be applied to the
associated channel.

Note: If the channel command value

1

is less than or equal to the low clamp value, the

under range status bit, for the associated channel, will be set.

The low clamp value must be less than the high clamp value or a
module fault will be generated. If both the low clamp and high
clamp values are left at zero, the output is clamped using the end
points of the associated channel’s defined output range

6.3.17 High Clamp Value (Words 5, 13, 21, 29)

The high clamp value determines the maximum analog signal that will be applied to the
associated channel.

Note: If the channel command value

1

is greater than or equal to the high clamp value,

the over range status bit, for the associated channel, will be set.

The low clamp value must be less than the high clamp value or a
module fault will be generated. If both the low clamp and high
clamp values are left at zero, the output is clamped using the end
points of the associated channel’s defined output range

6.3.18 Ramp Rate Value (Words 6, 14, 22, 30)

The ramp rate value defines the rate at which the output will change state once a channel
is commanded to a new value. The ramp rate is defined in terms of the selected
range/format in units per second. For example, in the 0 to 20mA DC range and percent
of full scale format, a ramp rate of 1000 is 10%/second or a maximum of 1mADC per
second. The following table describes the minimum ramp rate that can be applied for all
output range/types and output data formats.

Table 6-6 (Minimum Allowed Ramp Rates)
Output Data Format
Output Range/Type

Total Counts in Full

Scale

Number of Counts for

Every 1% of Ramp Rate

Real Units / Second for

Every 1% of Ramp Rate

Proportional

Counts

0 to 20mA

65534

655

0.2 mA/Sec

4 to 20mA

65534

655

0.16mA/Sec

Engineering

Units

0 to 20mA

21000

210

0.2 mA/Sec

4 to 20mA

17800

178

0.16mA/Sec

Scaled

for

PID

0 to 20mA

16383

164

0.2 mA/Sec

4 to 20mA

16383

164

0.16mA/Sec

Percent of Full Scale

0 to 20mA

10000

100

0.2 mA/Sec

4 to 20mA

10000

100

0.16mA/Sec

Note: If you enter a ramp rate value that is less than the minimum specified in the
table above, a module fault will be generated.

1

Module output words 0 through 3 for channel 0 through 3, respectively.

!

Attention

!

Attention