Spectrum Controls 1769sc-HART Modules User Manual
Page 20
Compact IO™ Isolated HART Analog Output Module
User’s Manual 0300217-03 Rev. A
3-2
Section 3.2
Power
Requirements
The module receives power through the bus interface from the +5V dc/ +24V dc system
power supply. The maximum current drawn by the module is shown in the table below.
Module Current Draw
at 5V dc
at 24V dc
180 mA
200 mA
Section 3.3 General
Considerations
Compact I/O is suitable for use in an industrial environment when installed in accordance
with these instructions. Specifically, this equipment is intended for use in clean, dry
environments (Pollution degree 2
1
and to circuits not exceeding Over Voltage Category
II
2
(IEC 60664-1)
3
3.3.1 Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-
hazardous locations only. The following WARNING statement applies to use in
hazardous locations.
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division2.
Do not replace components or disconnect equipment unless
power has been switched off or the area is known to be non-
hazardous.
Do not connect or disconnect components unless power has
been switched off or the area is known to be non-hazardous.
This product must be installed in an enclosure.
All wiring must comply with N.E.C. article 501-4(b).
3.3.2 Prevent Electrostatic Discharge
Electrostatic discharge can damage integrated circuits or
semiconductors if you touch analog I/O module bus connector pins or
the terminal block on the output module. Follow these guidelines when
you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When it is not in use, keep the module in its static-shield bag.
1
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
2
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
3
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
!