beautypg.com

Spectrum Controls 1769sc-HART Modules User Manual

Page 100

background image

Compact IO™ Isolated HART Analog Output Module

User’s Manual 0300217-03 Rev. A

7-34

Table 7-14 (HART Pass-Through Query Command)

HART pass through command complete query - command message packet structure

Field

Value

Definition

HART Channel
Number

0x00 – 0x03 (1 byte)

Module input
channel number for
HART command

Command Number

0x0C (1 byte)

The command
number

Handle (1

byte)

1-255

The handle from
command request
reply

If the data associated with the handle is not yet available, or invalid, the following reply
message will be returned.

Table 7-15 (HART Pass-Through Query Reply NOT SUCCESS)

HART pass through command complete query - reply packet structure

Field

Value

Definition

Unconnected Message Header
HART Channel
Number

0x00 – 0x07 (1 byte)

Module input
channel number for
HART command

Status (1

byte)

34 = DR_RUNNING
35 = DR_DEAD (bad request)

Command status

Count

(2 bytes) (Command Number 0x0C)

Length of Handle +
HART Response
Data in bytes (if
Success)

Handle

(1 byte)

The handle from
command complete
query

When data associated with the buffer becomes available, meaning a "success" response,
the reply will be formatted as follows:

Table 7-16 (HART Pass-Through Query Reply SUCCESS)

HART pass through command complete query - reply packet structure

Field

Value

Definition

Unconnected Message Header

HART Channel
Number

0x00 – 0x07 (1 byte)

Module input
channel number for
HART command

Status (1

byte)

00 = SUCCESS

Command status

Count

(1 byte) (Command Number 0x04)
(2 bytes) (Command Number 0x08, 0x0C)

Length of Handle +
HART Response
Data in bytes (if
Success)

Handle

1-255

The handle from
command complete
query

HART Command
Response Data

Size is the entire HART device response size
in bytes. The size does not include preambles
bytes.

The HART device’s
response to the
command (if
Success)