13 servicing, Maximum rate check and adjustment, Minimum rate check and adjustment – Glow-worm Ultracom sxi User Manual
Page 42: Re-check co2 and check the co/co2 combustion ratio, Gas rate check, Completion, 1 servicing
42
13 Servicing
RETAINING
STRAP
CONTROL
PANEL
13528
1. Maximum Rate Check and Adjustment
NOTE: To verify the maximum gas rate CO2 setting the
appliance must be checked at the maximum rate first.
Press the “reset” button on the controls fascia, release
and immediately press and hold in the “+” button. After
approximately 5 seconds “Hi” will be displayed. Pressing
the mode button when “Hi” is selected will force the boiler
to maximum rate, the display will flash between “Hi” and the
“default display” this will indicate the boiler has been forced to
maximum. Wait until the CO2 value is stable and check that
the value is within the range specified in table in the “check”
column.
If the combustion reading is not within the acceptable
values AND the integrity of the complete flue system and
combustion circuit seals have been verified and the inlet
gas pressure (and gas rate) have been verified, then, it will
necessary to adjust the combustion rate of the appliance.
NOTE: Adjustment is made by turning the gas valve
throttle an ⅛ of a turn, waiting 1 minute to allow the
appliance to stabilise before checking or making further
adjustments.
● Rotate the “throttle”(anti-clockwise to increase), to the
required CO2, refer to diagram 12.5 and the “SETTING”
column in the table.
● Exit the forced rate function, press the “mode” and “+”
buttons simultaneously, this will reset the boiler to the default
display. Now proceed to check the minimum rate adjustment.
2. Minimum Rate Check and Adjustment
● Now check the minimum gas rate CO2 setting: Press
and release the “reset” button on the controls fascia, then
immediately press and hold in either of the “+” buttons. After
approximately 5 seconds “Hi” will be displayed. Pressing the
“+” or “-” buttons will toggle between “Hi” and “Lo”. Press the
mode button when “Lo” is selected, this will force the boiler
to minimum rate and the display will flash “Lo”, indicating the
boiler is operating at minimum.
● Wait until the CO2 value is stable and check that the value
is within the range specified in table in the “check” column.
If adjustment is necessary, proceed as follows:
NOTE: Adjustment of the CO2 at minimum rate is very
coarse and should not be adjusted more than an ⅛ of
a turn at a time. Wait 1 minute to allow the appliance to
stabilise before checking or making further adjustments.
● Gradually rotate the “offset adjustment” (anti-clockwise to
decrease) to the required CO2, refer to diagram 12.5 and the
“SETTING” column in the table.
● Exit the minimum rate function, press the “mode” and “+”
buttons simultaneously, this will reset the boiler to the default
display.
3. Re-Check CO2 and check the CO/CO2
combustion ratio.
● Re-check the maximum and minimum CO2 values to
ensure that they are within the “setting” limits in the table
then check the CO/CO2 combustion ratio does not exceed
the value in the CO/CO2 column of the table. If the CO/CO2
setting exceeds the value in the table, a complete servicing of
the appliance will be necessary, refer to section 13.1.
If the CO2 and the CO/CO2 ratio falls within the tolerances
quoted, exit the function press the “mode” and “+” buttons
simultaneously, this will reset the boiler to the default display.
Remove the analyser probe and replace the cap on the
sampling point, replace the controls fascia, inner and front
casing panels.
IMPORTANT: Remember to replace the sample point cap on
completion of the test.
GAS RATE CHECK
Check the gas rates as described in the commissioning
section.
Diagram 13.3
COMPLETION
If it is not possible to achieve the required results for either
the combustion or gas rates, it will be necessary to complete
a full service of the appliance and then repeat the combustion
check procedure. If after servicing and adjustment of the
appliance the combustion values are still unacceptable
and after further remedial work has been carried out, the
appliance must be disconnected until the CO/CO2 ratio
is acceptable. Advice can be sought from the Glow-worm
Technical Helpline.
13.1 Servicing
NOTE: If the Combustion CO2, CO/CO2 ratio & Gas
rate checks did not require adjustment then it will not be
necessary to complete a full service.
All routine servicing requirements can be achieved by the
removal of the front panel, see diagram 13.2. Position the
control box into the service position, see diagram 13.3.
Before commencing with a service or replacement of parts.
The boiler should be isolated from the electrical and gas
supplies.