10.1 Flue Length

The maximum permissible horizontal flue length is 10 metres

plus the flue terminal assembly, this can be achieved by use

of the accessories, see diagram 10.3.
However should an additional 90o or 2 x 45o elbows be used

then the length MUST be reduced by 1metre.
The diagram 10.1 shows the length achievable by using the

kit A2043600.
When extension pipes are used the flue system must be

designed to have a continuous fall to the boiler of at least 2.5o

44mm/metre to allow condensate to run back into the boiler

and out via the condensate drain.
The flue can be installed from inside the building, when

access to the outside wall face is not practicable.

10 Telescopic Flue - Length, Preparation and Installation

Horizontal Telescopic Flue - Rear

Diagram 10.1

13558

13559

Ultracom

18sxi

Ultracom

30sxi

Exhaust mass rate (g/s)
At Min Thermal
Load (40C°/30°C)

2.30

2.45

At Max Thermal
Load (80C°/60°C)

8.75

13.25

Exhaust temperature (ºC)
At Min Thermal
Load (40C°/30°C)

56.0

44.0

At Max Thermal
Load (80C°/60°C)

69.0

57.0

Horizontal Telescopic Flue - Side

Multiple Boiler Chimney Flue Length

The flue length must be calculated and installed according to

the relevant standards EN 13384-1 and 2 (C43 flue systems

only) with reference to the table below and the manufacturers

instructions supplied.
The appliance maximum flue length must be included when

calculating the overall design of the flue system.