Creating an IP-852 Channel

Symptom

Probable Cause

Corrective Action

The IP-852 device

on the IP-852

channel pings

successfully, but

will not

commission.

Address translation

may take place

somewhere between

the two devices.

The router

application does not

exist.

Make sure that the IP address of the

target IP-852 device matches the IP

address defined for it in the IP-852

Configuration Server.

If you are using an i.LON 600 router,

determine if the router application
exists by using the listapp command in

the Console Application. Create the
router app with the createapp Router

command if it does not exist. If you are

using a SmartServer or i.LON 100

router, make sure the device is licensed

and configured to operate as an IP-852

router.