20
Creating an IP-852 Channel
Symptom
Probable Cause
Corrective Action
The IP-852 device
on the IP-852
channel pings
successfully, but
will not
commission.
Address translation
may take place
somewhere between
the two devices.
The router
application does not
exist.
Make sure that the IP address of the
target IP-852 device matches the IP
address defined for it in the IP-852
Configuration Server.
If you are using an i.LON 600 router,
determine if the router application
exists by using the listapp command in
the Console Application. Create the
router app with the createapp Router
command if it does not exist. If you are
using a SmartServer or i.LON 100
router, make sure the device is licensed
and configured to operate as an IP-852
router.