Verifying lonworks/ip-852 router functionality, Verifying l, Ip-852 router functionality – Echelon IP-852 Channel User Manual

Page 25

background image

IP-852 Channel User’s Guide

17

Figure 2.11 IP-852 Routers Configured on a L

ON

W

ORKS

Network

Verifying L

ON

W

ORKS

/IP-852 Router Functionality

You can verify that an IP-852 device that you have configured as a L

ON

W

ORKS

/IP-852

router is functioning as a L

ON

W

ORKS

network. You will typically use the network

management tool that you used to configure the IP-852 device as a L

ON

W

ORKS

router to

do the verification. This section describes how to use the LonMaker Integration Tool to

do the verification.
To verify that the IP-852 devices in the network shown in Figure 2.11 are working

correctly, right-click on the network variable connection between
DI-10 (switch) functional block and DO-10 (LED) function block and select Monitor
Input Value
. Verify that the value displayed on the connection in LonMaker is tracking
the value of the Digital Output network variable in DI-10 functional block. If you do not

see network variable updates reported by the LonMaker tool, there is a problem. Refer

to Table 2.2 for troubleshooting information.