500 Series Display Cases Service and Installation Manual

5

For customer service, call (800) 733-8829, (800) 773-8821, Fax (989) 773-3210, www.delfield.com

Pressure Control

The temperature is controlled by an adjustable pressure

control located in the machine compartment. An adjustable

control has the word COLDER near the knob, with an arrow

to indicate the adjustment direction. These controls are

field adjustable and do not require a service agent. If you

have any questions, feel free to contact the Delfield Service

Department.

The refrigeration systems on self-contained CR & OR models

were adjusted at the factory to maintain between 36°F and

40°F. No adjustment should be necessary. If adjustment

does become needed however, the factory recommended

settings are:

Low-pressure settings (CR models): 82 psi cut-in,

47 psi cut-out, 35 psi differential.

Low-pressure settings (OR models): 82 psi cut-in,

40 psi cut-out, 42 psi differential.

Operating pressures: High, 170 to 200 psi. Low, 30 to 37

psi.

In attempting to adjust the pressure control, you can

do damage to your unit by accidentally adjusting the

differential. Please make small incremental adjustments

if a temperature adjustment is necessary, please contact

the service department at Delfield (800) 733-8829 #1,

or your local service agent. Delfield is not responsible

for charges incurred while having the pressure control

adjusted.