Carrier 50DL User Manual
Page 4
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 1 — Physical Data
UNIT 50DL
044
054
064
OPERATING WEIGHT (lb)
Base Unit
5406
6100
6485
Economizer
225
250
250
Roof Curb
200
225
225
COMPRESSOR
Serviceable, Hermetic
Quantity...Type
2 06E
2. .06E*
2 06E
Quantity Cylinders (ea)...Rpm
4 1750
4 6 1750
6
1750
Capacity Steps (%) (Standard)
50, 100
60, 100
50, 100
With Accessory Unloaders
25, 50, 75, 100
20, 40, 60, 80, 100
16, 33, 50, 67, 83, 100
Capacity Steps (%) (Variable Volume)
With Electric Unloaders
25, 50, 75, 100
20, 40, 60, 80, 100
16, 33, 50, 67, 83, 100
REFRIGERANT CHARGE
Type 22; Controlled by Thermostatic Expansion Valve
System 1...System 2 (lb)
37 0 37 0
53 0 42 0
81 0 81 0
OUTDOOR AIR FANS
Direct Driven, Propeller Type
Quantity...Diameter (in.)
3 30
4 30
4 30
Nominal Cfm
21,000
28,000
31,000
Motor Hp...Rpm
1 1050
1 1050
1
1150
CONDENSER COIL
Rows...Fins/in.
3 158
3 158
4 15.8
Total Face Area (sq ft)
61 0
81 5
81 25
INDOOR AIR FANt
Belt Driven, Centrifugal Type
Quantity...Size (in.)
4 15x9
4 15x11
4 15x11
Maximum Allowable Rpm
1300
1300
1450
Nominal Cfm
Standard Motor and Drive
16,000
20,000
24,000
Motor Hp
Motor Frame Size
15
20
25
Single Speed
254T
256T
284T
Two Speed
284T
286T
286T
Fan Pulley Pitch Diameter (in.)
10
6
106
80
Fan Pulley Bore
I’Me
I’Me
Single-Speed Motor Rpm
1750
1750
1750
Two-Speed Motor Rpm
Motor Pulley Pitch Diameter (in.)
1750/1170
1750/1170
1750/1170
Pulley A
6
5
6
5
56
Pulley B
Resulting Fan Rpm
5 6
60
60
Single-Speed with Pulley A. .B
1073 925
1073 ..991
1225 1312
Two-Speed with Pullley A...B
1073/751
1073/751
1225/817.
925/617
991/661
1312/875
Alternate Motor and Drive
Motor Hp
Motor Frame Size
20
25t
30t
Single Speed
256T
284T
286T
Two Speed
286T
286T
—
Fan Pulley Pitch Diameter (in.)
80
80
10
6
Fan Pulley Bore
I'Me
I'Me
Single-Speed Motor Rpm
1750
1750
1750
Two-Speed Motor Rpm
Motor Pulley Pitch Diameter (in.)
1750/1170
1750/1170
1750/1170
Pulley A
5 3
5 3
8
0
Pulley B
5 6
5 6
**
Resulting Fan Rpm
«
Single-Speed with Pulley A...B
1159 1225*
1159 1225
1321 —
Two-Speed with Pulley A...B
1159/773.
1225/817
1159/773.
1225/817
1321/881
EXHAUST FAN MOTOR Quantity...Hp
2 3
2 3
2 3
EVAPQRATQR CQIL
Rows...Fins/in
4 15
4 15
4 139
Total Face Area (sq ft)
30 2
35 4
35 4
ELECTRIC RESISTANCE HEATERS
Open Nichrome Wire Elements with Multiple-Stage Control
HeatikW
See Electrical Data tables
INDQQR AIR FILTERS
No. ...Size
27 16x25
9 20x25
9 20x25
Standard; 2-in Throwaway
21 16x25
21 16x25
Bag Type; 12-in. (Optional)
6
12x24
7 12x24
6
24x24
7 24x24
*Unit contains one 06EA250 and one 06EA275 compressor
tStandard fan motor supplied with standard fan drive pulleys and
belts; alternate fan motor supplied with alternate fan drive
pulleys and belts Other combinations are field supplied Pulley
A is installed in unit; Pulley B is shipped with unit (044 and 054).
JDue to large frame size, the 25-hp, 208-230-volt and 30-hp
motors are available in single speed only
**The 50DL064 alternate drive is supplied with Pulley A only
288