beautypg.com

Service – Carrier 50DL User Manual

Page 16

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

pressor automatically restarts after a 5-minute inter­
val. If compressor shutdown is due to tripped over­
loads, the circuit breakers must be manually reset

before compressor will start.

Timer (Time Guard®) for second compressor has

a 6-minute interval to prevent compressors from
starting simultaneously.

Refer to unit label diagram for specific timer

sequence.
CRANKCASE HEATER — Unit main power

supply must remain on to provide crankcase heater
operation. Crankcase heater in each compressor
keeps oil free of refrigerant while compressor is off.

HEAD PRESSURE CONTROL — Each unit has a

fan cycling thermostat to shut off 2 outdoor fan
motors at 55 F. This permits unit to operate with
correct condensing temperatures down to 35 F out­
door air temperature.

SERVICE

Electronic Component Checkout

CONSTANT VOLUME UNITS

The checkout procedures in this section will

determine whether;

1. The logic panel is controlling the heating and

cooling equipment properly.

2. System components are correctly wired to the

logic panel.

Prior to checking out control circuit, establish

setting on the low ambient lockout thermostat.
Compressors will not start below this setting (cool­
ing mode only). Recommended setting is approxi­
mately 50-55 F.

NOTE: To complete the electronic component
checkout, a volt-ohmmeter (Simpson 260 is
recommended) is required.

LOGIC PANEL (Fig. 21)

1. Check that 24 VAC is supplied to logic panel.

Connect meter to terminals TR.

2. Check thermostat supply voltage at STAT ter­

minals 1 and 2. Reading should be 20 VDC.

3. Remove thermostat supply wires from STAT

terminals 1 thru 5 on logic panel.

4. Set meter to volts AC scale equal to relay switch­

ing voltage (50-volt scale for 24 VAC).

5. To simulate a call for cooling, jumper between

STAT terminals 2 and 4. Normally open Logic
Panel contacts (Cool 1 and 2) should close and
cooling equipment should cycle on.

6. Connect meter leads to the normally open cool­

ing contacts 1 and 2 on logic panel. Meter should

Fig. 21 — Logic Panel

read zero if contacts have closed and contacts
are made.

If meter is reading zero and cooling equipment
has not cycled on, logic panel is not at fault.

7. To simulate a call for heating, jumper between

STAT terminals 2 and 5. Normally open logic
panel contacts (HEAT 1 and 2) should close and
heating equipment should cycle on.

8. Connect meter leads to the normally open heat­

ing contacts on logic panel. Meter should read
zero if contacts have closed.

If meter is reading zero and heating equipment
has not cycled on, logic panel is not at fault.

9. Replace thermostat wiring to terminals 1 thru 5.

DISCHARGE SENSOR

1. Set resistance on meter to R x 100.

2. Disconnect lead from SENSOR terminal T1 on

logic panel.

3. Connect one meter lead to logic panel terminal T

and the other meter lead to the loose lead wire
from the sensor.

4. Meter readings depend on temperature. Dis­

charge sensor readings should be between 1500
and 4500 ohms. See Fig. 22.

THERMOSTAT/TRANSMITTER (Fig. 16)

1. Set meter to 20 VDC scale.

2. Check for power to thermostat. Connect negative

(-) lead to terminal 1 and positive (+) lead to
terminal 2. Meter should read 20 VDC.

3. Connect the negative (-) lead to terminal 1 and

the positive (+) lead to terminal 4.

4. Slowly move the cooling lever below room tem­

perature to simulate a call for cooling. Meter

16