(A) HEATING SETBACK

(B) COOLING SETUP OR LOCKOUT

Fig. 15 — Setback/Setup Module (Partial)

5. Remove cover from thermostat (or from trans­

mitter if a remote sensor is used); note the red
diagnostic light-emitting diodes (LED’s). See
Fig. 16.

6. To call for cooling, move the thermostat or

transmitter cooling set point (blue lever) below

room temperature. Cooling LED on the right-
hand side of thermostat or transmitter should
begin to glow. Check the cooling effect at supply
duct outlets.If the mechanical cooling does not
come on, see Service, Electronic Component

Checkout.

7. Move the thermostat or transmitter cooling set

point above room temperature. The cooling
equipment should cycle off and the cooling

LED intensity should decrease to a faint glow
or go off completely. The economizer should
move to minimum position.

To Shut Off Unit — For standard units, set the
subbase selector switch to OFF or set the cooling
temperature selector lever above room tempera­
ture. For units with Energy Management option, set

the cooling temperature selector switch above
room temperature.

Do not shut off unit circuit breakers except

when unit is serviced. Crankcase heater is ener­

gized only when unit power is on.

HEATING (Electric Heat Units)

1. Turn on unit power; set circuit breakers at ON.

2. On units with Energy Management option, posi­

tion the HEAT SETBACK SELECT switch in
the setback/setup module to the desired position
(5°, 10°, or 15°). See Fig. 15.

3. Move the thermostat or transmitter heating set

point (red lever) above room temperature. The

HEATING
LEVER (RED)

COOLING
LEVER(BLUE)

COVER

THERMOSTAT/TRANSMITTER

Fig. 16 — Electronic Thermostat/Transmitter (Without Subbase)