Start-up, Constant volume units, I -gíítíf – Carrier 50DL User Manual
Page 10
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 3 — Electrical Data — 50DL064
MODEL
VOLTAGE
COMPR
COMPR
OUTDOOR
FAN
INDOOR
FAN
EXHAUST
FAN
HEATERS
POWER
NOMINAL
VOLTS-PH-HZ
RANGE
NO. 1
NO. 2
MOTORS
MOTOR
MOTOR
SUPPLY
Min
Max
RLA
LRA
RLA
LRA
Qty
FLA
Hp
FLA
Hp
FLA
kW
FLA
MCA
MOCP*
25
75
—
—
—
—
370
400
25
75
3
11
—
—
392
450
30
88
—
—
—
—
383
450
25
75
—
—
60/73 2
166/184
370
450
25
75
—
—
75/91 5
208/230
370/382
500
50DL064
187
254
119
506
119
506
4
6 6/6 0
30
88
3
11
_
_
405
450
208/230-3-60
25
75
3
11
60/73 2
166/184
392
450
25
75
3
11
75/91 5
208/230
392
500
30
88
—
—
60/73 2
166/184
383
500
30
88
—
—
75/91 5
208/230
383/398
500
30
88
3
11
60/73 2
166/184
405
500
30
88
3
11
75/91 5
208/230
405
500
25
34
—
—
—
—
166
200
25
34
3
48
—
—
175
200
30
40
—
—
—
—
172
200
25
34
—
—
73 2
92
166
225
25
34
—
—
91 5
115
187
250
50DL064
460-3-60
414
508
53
253
53
253
4
30
30
25
40
34
3
3
48
48
73 2
92
181
175
200
225
25
34
3
48
91 5
115
187
250
30
40
—
—
73 2
92
172
250
30
40
—
—
91 5
115
194
250
30
40
3
48
73 2
92
181
250
30
40
3
48
91 5
115
194
250
LEGEND (Tables 2 and 3)
Compr
— Compressor
FLA
— Full Load Amps
Hp
— Nominal Horsepower
kW
— Kilowatts
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Ampacity
MOCP
— Maximum Overcurrent Protection
RLA
— Rated Load Amps
*Fuse only.
NOTES (Tables 2 and 3)
1 All outdoor fan motors are single-phase motors
2 All heaters are 3-phase assemblies
3 Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase unbalance in supply volt
age is greater than 2% Use the following formula to determine
the % voltage unbalance
% Voltage Unbalance
max voltage deviation from average voltage
Example:
A B
Supply voltage is 460-3-60
AB = 452 volts
BC = 464 volts
AC = 455 volts
Average Voltage =
452 + 464 -r 455
1371
= 457
100
X -
Determine maximum deviation from average voltage
(AB) 457 - 452 = 5 volts
(BC) 464 - 457 = 7 volts
(AC) 457 - 455 = 2 volts
Maximum deviation is 7 volts
Determine % voltage unbalance
% Voltage Unbalance = 100 x - ~ = 1 53%
“
457
This amount of phase unbalance is satisfactory as it is below
the maximum allowable 2%
¿i
-gíítíf
average voltage
START-UP
Constant Volume Units
COOLING (WITH OR WITHOUT ENERGY
MANAGEMENT OPTION)
1. Open compressor service valves. Make sure the
crankcase heater has been on for at least 24 hours
to remove liquid refrigerant from compressor
crankcase. Check compressor oil level. Oil sight
glass should be half full.
2. Be sure that the liquid line service valve is open
and that high- and low-side refrigerant service
ports are closed as applicable.
3. On units equipped with the Energy Management
option, move the COOL SETUP SELECT
jumper wire to the desired setting(5°, 8°, or 12°).
If cooling is not desired during the unoccupied
periods, move jumper wire from COOL SETUP
to COOL LOCKOUT. See Fig. 15.
4. Turn on power to unit. On standard units, set the
subbase selector switch to COOL. On units with
the Energy Management option, set the 7-day
time clock as required. Refer to 7-Day Time
Clock Adjustment. Check that compressor low
ambient lockout contacts and morning warm-up
contacts (on units with Energy Management
option) are closed.
10