beautypg.com

Start-up, Constant volume units, I -gíítíf – Carrier 50DL User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 3 — Electrical Data — 50DL064

MODEL

VOLTAGE

COMPR

COMPR

OUTDOOR

FAN

INDOOR

FAN

EXHAUST

FAN

HEATERS

POWER

NOMINAL

VOLTS-PH-HZ

RANGE

NO. 1

NO. 2

MOTORS

MOTOR

MOTOR

SUPPLY

Min

Max

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

Hp

FLA

kW

FLA

MCA

MOCP*

25

75

370

400

25

75

3

11

392

450

30

88

383

450

25

75

60/73 2

166/184

370

450

25

75

75/91 5

208/230

370/382

500

50DL064

187

254

119

506

119

506

4

6 6/6 0

30

88

3

11

_

_

405

450

208/230-3-60

25

75

3

11

60/73 2

166/184

392

450

25

75

3

11

75/91 5

208/230

392

500

30

88

60/73 2

166/184

383

500

30

88

75/91 5

208/230

383/398

500

30

88

3

11

60/73 2

166/184

405

500

30

88

3

11

75/91 5

208/230

405

500

25

34

166

200

25

34

3

48

175

200

30

40

172

200

25

34

73 2

92

166

225

25

34

91 5

115

187

250

50DL064

460-3-60

414

508

53

253

53

253

4

30

30
25

40
34

3
3

48
48

73 2

92

181
175

200
225

25

34

3

48

91 5

115

187

250

30

40

73 2

92

172

250

30

40

91 5

115

194

250

30

40

3

48

73 2

92

181

250

30

40

3

48

91 5

115

194

250

LEGEND (Tables 2 and 3)

Compr

— Compressor

FLA

— Full Load Amps

Hp

— Nominal Horsepower

kW

— Kilowatts

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Ampacity

MOCP

— Maximum Overcurrent Protection

RLA

— Rated Load Amps

*Fuse only.

NOTES (Tables 2 and 3)
1 All outdoor fan motors are single-phase motors
2 All heaters are 3-phase assemblies
3 Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase unbalance in supply volt­
age is greater than 2% Use the following formula to determine

the % voltage unbalance

% Voltage Unbalance

max voltage deviation from average voltage

Example:

A B

Supply voltage is 460-3-60

AB = 452 volts

BC = 464 volts
AC = 455 volts

Average Voltage =

452 + 464 -r 455

1371

= 457

100

X -

Determine maximum deviation from average voltage

(AB) 457 - 452 = 5 volts
(BC) 464 - 457 = 7 volts
(AC) 457 - 455 = 2 volts

Maximum deviation is 7 volts
Determine % voltage unbalance

% Voltage Unbalance = 100 x - ~ = 1 53%

457

This amount of phase unbalance is satisfactory as it is below
the maximum allowable 2%

¿i

-gíítíf

average voltage

START-UP

Constant Volume Units

COOLING (WITH OR WITHOUT ENERGY

MANAGEMENT OPTION)

1. Open compressor service valves. Make sure the

crankcase heater has been on for at least 24 hours
to remove liquid refrigerant from compressor
crankcase. Check compressor oil level. Oil sight
glass should be half full.

2. Be sure that the liquid line service valve is open

and that high- and low-side refrigerant service
ports are closed as applicable.

3. On units equipped with the Energy Management

option, move the COOL SETUP SELECT

jumper wire to the desired setting(5°, 8°, or 12°).

If cooling is not desired during the unoccupied
periods, move jumper wire from COOL SETUP
to COOL LOCKOUT. See Fig. 15.

4. Turn on power to unit. On standard units, set the

subbase selector switch to COOL. On units with
the Energy Management option, set the 7-day
time clock as required. Refer to 7-Day Time

Clock Adjustment. Check that compressor low
ambient lockout contacts and morning warm-up
contacts (on units with Energy Management
option) are closed.

10