beautypg.com

Symptom and probable cause – Carrier WEATHERMASTER III 38HQ User Manual

Page 18

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TROUBLESHOOTING GUIDE — HEATING

SYMPTOM AND PROBABLE CAUSE

NO HEATING (Compressor Will Not Run)

1. Main power circuit open due to faulty power

supply.

2. Control power circuit open or faulty.

3. Defrost control malfunctioning.

4. Signal-Loc™ malfunction.

INSUFFICIENT HEATING (Compressor Runs or

Cycles)

1. Low suction and low head pressure due to

coil obstruction in airflow or refrigerant circuit.

2. High suction, low superheat.

3. Frozen outdoor coil.

4. Accessory electric resistance heaters not

operating.

5. High suction, low head pressures (caused by

refrigerant system or indoor fan problem).

6. Low suction, high head pressures (may be

accompanied by low airflow at air outlets).

7. Compressor no. 2 fails to start due to failure of

outdoor thermostat.

PROBABLE REMEDY

1

.

Check power supply, main power wire connec­

tions, fuses. See Electrical Data.

2. Check low voltage transformer, remote control

center, control relay and contacts, timer relay and

motor, compressor overloads and pressurestats

for faulty operation. Review component headings

in Service section. Check unit label diagram(s).

3. Check Defrost control procedure to be sure defrost

thermostat and relay are operational.

4. Check wire connections. Check continuity thru

terminals 2 and 3 Check to see if power wire has

been routed thru current loop.

1 Check coil for obstruction (dirt, debris). Check that

outdoor air fan is correctly positioned and turns
freely. Review fan clearance requirements and
coil cleaning procedure. Check liquid line drier,
AccuRater.

2. Check refrigerant flow device Check refrigerant

charge.

3. Check fan operation, coil cleanliness. Check

defrost control circuit. Check refrigerant charge
(use Charging Charts and/or Operational Check
Charts).

4. Check heater power supply, outdoor thermostats

and their settings Check that heater elements are

not broken.

5. Reversing valve may be leaking or "hung-up "

Check valve and its solenoid for correct operation
Replace if suspect

Indoor fan motor capacitor may be defective
Replace capacitor Fan may be cycling on over­
loads. Check overloads, loose terminal connec­

tions Fan motor may be burned out. Check and
replace or lubricate See Fan Adjustment. Replace
or repair motor or fan as necessary.

6. Check for restricted refrigerant system com­

ponent. Check Heating Operational Check charts
to detect even charge. Check system for non­
condensables. Refer to Standard Service Tech­

niques Manual, Chapter 1, Refrigerants.

7 Check outdoor ambient switch. Switch should be

closed when ambient is below switch set point.

18