beautypg.com

Carrier WEATHERMASTER III 38HQ User Manual

Page 17

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TROUBLESHOOTING GUIDE — COOLING

SYMPTOM AND PROBABLE CAUSE

PROBABLE REMEDY

/■

r

\

COMPRESSOR WILL NOT RUN OR SHUTS
OFF — WILL NOT RESTART

Contactor open

1. Burned out transformer, open thermostat

circuit, open overload.

2. Power supply interrupted.

3. Power circuit is open due to loose electrical

connection, open compressor safety device.

Contactor or coil defective.

4. Signal-Loc™ malfunction.

Contactor Closed, or Closes then Opens

1. Compressor power is out, compressor motor is

burned out or internal overloads are open.

Timer circuit (clock or switch) is faulty.

2. Compressor stuck.

3. Control circuit open due to faulty low-voltage

transformer or defective control circuit

compartment.

COMPRESSOR RUNS BUT COOLING IS

INSUFFICIENT

1. Low suction pressure or incorrect superheat.

2. Restricted airflow due to dirty filters, duct

obstruction or indoor coil icing. Refrigerant
system obstructed. Filter-drier obstructed or
refrigerant flow is insufficient.

3. High suction pressure/low head pressure due

to open internal pressure relief, defective com­

pressor valves or faulty reversing valve.

4. High suction pressure/low superheat (com­

pressor may be flooding).

COMPRESSOR CYCLES ON AND OFF

1. Internal overloads are opening or refrigerant

system is dirty. High or low pressure switch is
opening.

2. Faulty timer or defrost control operation.

Run capacitor faulty.

3. Fan motors operate intermittently.

4. Reversing valve in mid-position.

1. Check control circuit component and wiring. Refer

to unit label diagram, check all safety devices.

Refer to Standard Service Techniques Manual,
Chapter 2, Electrical.

2. Check for blown fuses or tripped circuit breakers.

3. Check power wire connection for tightness. Check

compressor internal thermostat, overloads (see

label diagram). Check contactor, replace if
defective.

4. Check wire connections. Check continuity thru

terminals 2 and 3. Check to see if power wire has

been routed thru current loop.

1. Check main power supply and wiring. Refer to

Electrical Data table and label diagram. Check

defrost timer circuit relay. Check defrost control
contacts. Replace defective controls.

2. Check start capacitor. Check compressor motor

windings.

3. Review label diagrams. Check control power

wires, connections. Check control transformer

power output (24 v). Check remote control center

contacts and temperature settings.

1 Check Refrigerant Charging procedure, charging

charts. Check AccuRater™ for proper piston.

2. Check indoor air system for obstructions — dirty

filters, ductwork debris, improper fan speed.

Expansion valve or AccuRater improperly sized.

3. Check Carrier Compressor Service Manual for

compressor repair procedures. See Compressor

Removal. Check reversing valve solenoid opera­
tion and valve seats.

4. Check refrigerant flow device Check that maxi­

mum elevation between indoor and outdoor units
is not too great Check refrigerant charge

1. Check refrigerant system for noncondensables, or

improper charge. See Refrigerant Charging.
Check for airflow obstructions See Coil Cleaning.

2. Check timer or defrost control relays and con­

tacts. Replace fun capacitor.

3. Check motor leads and overloads.

4. Check reversing valve solenoid. See label diagram.

Check that dirt in refrigerant system does not
cause valve to "hang up."

17