beautypg.com

Carrier WEATHERMASTER III 38HQ User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

charge, evacuate system to 500 microns (29.7 in.
vacuum) before recharging. Service port connec­
tions are provided on indoor compressor unit

suction and discharge lines for evacuation and
charging. (See Fig. 14 for service port location.)

Dial-a-charge charging cylinder is an accurate de­

vice used to recharge systems by weight. The
cylinders are available at refrigeration supply
firms.

TO CHECK AND/ OR ADJUST CHARGE DUR­

ING COOLING SEASON — Use correct Cooling
Cycle Charging Chart (Fig. 10 and 11) and follow
charging chart usage method below.

TO CHECK SYSTEM OPERATION DURING
HEATING CYCLE — Use correct Heating Cycle
Operation Check Chart (Fig. 12 and 13). These
charts indicate whether a correct relationship
exists between system operating pressures and air
temperatures entering indoor and outdoor units. If
pressure and temperature lines do not intersect on
chart, the system refrigerant charge may not be
correct or other system abnormalities may exist.

Do not use Operation Check Charts to adjust
refrigerant charge. Weigh charge into system.

U S I N G C O O L I N G C Y C L E C H A R G I N G
CHARTS

1. Operate unit a minimum of 10 minutes before

checking

charge,

and

after

each

charge

adjustment.

2. Measure suction pressure by attaching a gage to

indoor unit suction service port. (See Fig. 14 for
correct service port location.)

3. Measure outdoor air dry-bulb temperature enter­

ing outdoor coil. Use a service thermometer.

4. Using a sling psychrometer, measure wet-bulb

temperature of air entering indoor fan-coil
unit.

5. Refer to correct Charging Chart. Locate on

curves where outdoor air dry-bulb and indoor air
wet-bulb temperature lines intersect.

6. From intersect point, project vertically down­

ward to chart suction pressure line. Compare
chart suction pressure to unit suction pressure
(Step 2).

7. If unit suction pressure is lower than chart pres­

sure, add refrigerant to system until chart pres­
sure is reached. If unit suction pressure is

higher than chart pressure, remove refrigerant
until chart pressure is reached.

Temporary Capacitance Boost — If necessary, see
Carrier Standard Service Techniques Manual,
Chapter 2, Electrical, for details.

SUCTION PRESSURE {PSIG) AT SERVICE PORT

Fig. 10 — 38HQ227/38HQ940 with

28VQ036/40FS160 Cooling Cycle

Charging Chart

t

Fig. 11 — 38HQ234/38HQ960 with

28VQ042/40FS200 Cooling Cycle

Charging Chart

12