beautypg.com

A caution – Carrier WEATHERMAKER 8000 58WAV User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

24-V WIRING — Make field 24-v connections at the 24-v tenni-

nal strip. (See Fig. 9.) Connect terminal Y as shown in Fig. 8 for

proper cooling operation. Use only AWG No. 18, color coded

copper thermostat wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located

on the main control board. Any direct shorts during installation,

service, or maintenance could cause this fuse to blow. If fuse

replacement is required, use ONLY a 3-amp fuse of identical size.
ACCESSORIES

1. Electronic Air Cleaner (EAC)

Two screw terminals (EAC-1 and EAC-2) are provided for

EAC connection. The terminals are energized with 115-v,

1-amp maximum during blower motor operation.

2. Humidifier (HUM)

Screw terminals (HUM-1 and C) are provided for 24-v

humidifier connection. The terminals are energized with 24-v,

0.5-amp maximum during heating blower motor operation.

Step 7— Venting

Refer to the enclosed Installation Instructions, GAMA Venting

Tables for Category I Furnaces, and QUIK'VENT™ Tables for

Category I Fan-Assisted Furnaces. The horizontal portion of the

venting system shall maintain a minimum of 1/4-in. upward slope

per linear ft and it shall be rigidly supported every 5 ft or less with

hangers or straps to ensure that there will be no movement after

installation.

Step 8—Start-Up, Adjustment, and Safety Check

GENERAL — The furnace must have a 115-v power supply

properly connected and grounded. Proper polarity must be main­

tained for correct operation. Thermostat wire connections at R, W,

C, and Y must be made at the 24-v terminal block on the control

board. The gas service pressure must not exceed 0.5 psig (14-in.

wc), but must be no less than 0.16 psig (4.5-in. wc).

A

CAUTION

This furnace is equipped with a manual reset limit switch in

the gas control area. The switch opens and shuts off power to

the gas valve if a flame rollout or over heating condition

occurs in the gas control area. DO NOT bypass the switch.

Correct inadequate combustion air supply problem and reset

the switch.

Before operating the furnace, check each manual reset switch for

continuity. If necessary, press the button to reset the switch.
The blower compartment door must be in place to complete the

115-v circuit to the furnace.

SEOUENCE OF OPERATION — Using the schematic diagram

shown in Fig. 10, follow the sequence of operation through the

different modes. Read and follow the wiring diagram very care­

fully.

NOTE:

If there is a power interruption on any thermostat call, the

control initiates a 90-sec blower only on period before starting

another cycle.

1. Heating mode

When the wall thermostat "calls for heat," the R-W circuit

closes. The furnace control performs a self-check, verifies the

pressure switch contacts are open, and starts the inducer

motor.

a. Prepurge period—As the inducer motor comes up to speed,

the pressure switch contacts close to begin a 15-sec

prepurge period.

b. Ignitor warm-up—At the end of the prepurge period, the

ignitor is energized for a 17-sec ignitor warm-up period. If

ignition is not established during the first cycle, the next

warm-up period is increased to 45 sec. All subsequent

ignition cycles will be 45 sec, or until the 115-v power

supply is interrupted. By interrupting the 115-v power

supply, the warm-up period is automatically reset to 17 sec.

c. Ignition sequence—When the ignitor warm-up period is

completed, the gas valve opens, permitting gas flow to the

burners where it is ignited. After 5 sec, the ignitor is

de-energized and a 2-sec flame-sensing period begins.

d. Flame-sensing—When burner flame is sensed, the control

begins the blower on delay period and continues holding

the gas valve open. If burner flame is not sensed, the

control closes the gas valve and repeats ignition cycle.

e. Blower on delay—Forty sec after burner flame is proven,

the blower motor is energized on heating speed. Simulta­

neously, the humidifier and electronic air cleaner terminals

(HUM-1 and C for humidifier, EAC-1 and EAC-2 for

electronic air cleaner) are energized. Jumper JW9

SHOULD NOT be cut. If jumper JW9 has been cut, the

blower on delay will be 60 sec.

f. Blower off delay—When the thermostat is satisfied, the

circuit between R-W is broken, de-energizing the gas valve

and stopping gas flow to the burners. The blower motor,

humidifier, and air cleaner remain energized 90, 135, 180,

or 225 sec (depending on the blower off time selection).

The furnace is factory set for a 135-sec blower off delay.

g. Post-purge period —The inducer motor remains energized

5 sec after the burners are extinguished. Jumper JW9

should not be cut. If jumper JW9 has been cut, the

post-purge period is 15 sec.

2. Cooling mode

When the thermostat "calls for cooling" R-Y circuit closes.

The R-Y circuit starts the outdoor condensing unit and starts

the furnace blower motor on cooling speed. The EAC termi­

nals are energized with 115v when the blower is operating on

cooling speed.
When the thermostat is satisfied, R-Y circuit is broken. The

condensing unit stops and the furnace blower continues

operating on cooling speed for an additional 90 sec.

3. Continuous blower mode

When the R-G circuit is made, the blower motor operates on

heating speed. During a "call for heat" the blower stops,

f

allowing the furnace heat exchangers to heat up more quickly,

then restarts at the end of the 40 sec blower on delay period.

Jumper JW9 should not be cut. If jumper JW9 has been cut,

the blower on delay will be 60 sec.
The blower reverts to continuous operation after the heating

cycle is completed.
When the thermostat "calls for cooling," the blower operates

on cooling speed. When the thermostat is satisfied, the blower

operates an additional 90 sec before reverting back to con­

tinuous operation on heating speed. EAC and HUM-1 termi­

nals are energized.

4. Heat pump mode

When installed with a heat pump, the furnace control auto­

matically changes the timing sequence to avoid long blower

off time during demand defrost cycles. When the W-Y or

W-Y-G thermostat inputs are received at the same time, the

control changes the blower to heating speed or starts the

blower if it was off, and begins a heating cycle. The blower