beautypg.com

Step 1—location, A caution, For example – Carrier WEATHERMAKER 8000 58WAV User Manual

Page 3: Ci-aning

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

step 1—Location

GENERAL

A

CAUTION

Do not install furnace in a corrosive or contaminated atmo­

sphere. Make sure all combustion and circulating air require­

ments are met, in addition to all local codes and ordinances.

A

CAUTION

Do not use this furnace during construction when adhesives,

sealers, and/or new carpets are being installed. If the furnace

is required during construction, use clean outside air for

combustion and ventilation. Compounds of chlorine and

fluorine when burned with combustion air form acids which

will cause corrosion of the heat exchangers and metal vent

system. Some of these compounds are found in paneling and

dry wall adhesives, paints, thinners, masonry

Ci-aning

mate­

rials, and many other solvents commonly used

in

ihe con­

struction process.

This furnace must be installed so the electrical components are

protected from water.
Locate the furnace close to the chimney/vent and as near the center

of the air distribution system as possible. The furnace should be

installed as level as possible.
When a furnace is installed so that the supply ducts carry air to

areas outside the space containing the furnace, the return air must

also be handled by a duct(s) ’ sealed to the furnace casing and

terminating outside the space containing the furnace.
Provide ample space for servicing and cleaning. Always comply

with the minimum fire protection clearances shown on the unit

rating plate.
LOCATION RELATIVE TO COOLING EQUIPMENT - The

cooling coil must be installed parallel with or on the downstream

side of the furnace to avoid condensation in the heat exchangers.

When installed parallel with a furnace, dampers or other means

used to control the flow of air must prevent chilled air from

entering the unit. If the dampers are manually operated, they must

be equipped with means to prevent operation of either unit unless

the damper is in the full-heat or full-cool position.
HAZARDOUS LOCATIONS - When the furnace is installed in

a residential garage, it must be installed so that the burners and

ignition source are at least 18 in. above the floor. The furnace

should be protected from physical damage by vehicles. When a

furnace is installed in public garages, airplane hangars, or other

buildings having hazardous atmospheres, the unit must be installed

in accordance with the recommended good practice requirements

of the National Fite Protection Association, Inc.

Step 2—Air For Combustion and Ventilation

Provisions for adequate combustion and ventilation air must be

provided in accordance with Section 5.3, Air for Combustion and

Ventilation, of the NFGC or applicable provisions of the local

building codes.
Canadian installations must be installed in accordance with NSC-

NGPIC and all authorities having jurisdiction.

A

CAUTION

Air for combustion must not be contaminated by halogen

compounds, which include fluoride, chloride, bromide, and

iodide. These elements are found in aerosol sprays, deter­

gents, bleaches, cleaning solvents, salts, air fresheners, and

other household products.

All fuel-burning equipment must be supplied with air for combus­

tion of the fuel. Sufficient air MUST be provided to ensure there

will not be a negative pressure in the equipment room or space. In

addition, a positive seal MUST be made between the furnace

cabinet and the return-air duct to prevent pulling air from the

burner area and draft safeguard opening.

A

CAUTION

The operation of exhaust fans, kitchen ventilation fans,

clothes dryers, or fireplaces could create a NEGATIVE

PRESSURE CONDITION at the furnace. Make-up air MUST

BE PROVIDED for the ventilation devices, in addition to that

required by the furnace.

Combustion air requirements are determined by whether the

furnace is in an UNCONFINED or CONFINED space.
UNCONFINED SPACE — An unconfined space must have at

least 50 cu ft for each 1000 Btuh of input for all the appliances

(such as furnaces, clothes dryer, water heaters, etc.) in the space.

For Example:

58WAV FURNACE

INPUT BTUH

MINIMUM SQ FT WITH

7-1/2 FT CEILING

44,000

293

66,000

440

88,000

587

110,000

733

132,000

880

154,000

1026

If the unconfined space is of unusually tight construction, air for

combustion and ventilation MUST come from either the outdoors

or spaces freely communicating with the outdoors. Combustion

and ventilation openings must be sized the same as for a confined

space. A minimum opening with a total of at least 1 sq in. per 5000

Btuh of total input rating for all equipment must be provided.

Return air must not be taken from the room, unless an equal or

greater amount of air is supplied to the room.
CONFINED SPACE — A confined space is one whose volume is

less than 50 cu ft per 1000 Btuh of the total output rating for all

appliances installed in that space. A confined space MUST have 2

permanent openings, 1 within 12 in. of the ceiling and the other

within 12 in. of the floor. (See Fig. 2.)

NOTE:

In determining the free area of an opening, the blocking

effect of the louvers, grilles, and screens must be considered. If the

free area of a louver or grille design is unknown, it may be

assumed that wood louvers have a 20 percent free area and metal

louvers or grilles have a 60 percent free area. Screens, when used,

must not be smaller than 1/4-in. mesh. Louvers and grilles must be

constructed so they cannot be closed.
The size of the openings depends upon whether the air comes from

inside or outside of the structure.

1. All air from inside the structure:

Each opening MUST have at least 1 sq in. of free area per

1000 Btuh of the total input for all equipment within the

confined space, but not less than 100 sq in. per opening. (See

Fig. 2.)