A warning, A caution – Carrier WEATHERMAKER 8000 58WAV User Manual
Page 7
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
------- FIELD 24-VOLT WIRING
------- FIELD 115-, 208/230-, 460-VOLT WIRING
------- FACTORY 24-VOLT WIRING
------- FACTORY 115-VOLT WIRING
FOUR
WIRE
VHT^_____________WHJ
—
£--------
^GND
115-VOLT FIELD-
SUPPLIED
FUSED
DISCONNECT
THERMOSTAT
TERMINALS
q
y.
q
GND
(!>■
©"
AUXILIARY
J-BOX
CONTROL
BOX
24-VOLT
TERMINAL
BLOCK
FIELD-SUPPLIED
FUSED DISCONNECT
•-
3
•Ч1-*-
—
—
I
-Jt-
-
4
—
-GND
208/230- OR
460-VOLT
THREE
PHASE
208/230-
VOLT
SINGLE
PHASE
CONDENSING
UNIT
FURNACE
• T W O
WIRE
NOTE: Connect Y-terminal as
shown for proper
operation.
Table 5—Electrical Data
NOTE: If any of the original wire,
as supplied, must be replaced, use
same type or equivalent wire.
UNIT
SIZE
VOLTS-
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
MAX
UNIT
AMPS
MIN
WIRE
GAGE
MAX WIRE
LENGTH (FT)t
MAX FUSE OR
HA14R-TYPE
14KT BKR AMPSt
Max*
Min*
045-08
115—60—1
127
104
6.0
14
47
15
045-12
115—60—1
127
104
8.3
14
34
15
070-08
115—60—1
127
104
5.9
14
47
15
070-12
115—60—1
127
104
8.7
14
32
15
091-14
115—60—1
127
104
9.0
14
31
15
091-16
115—60—1
127
104
10.4
14
27
15
111-12
115^60—1
127
104
8.0
14
35
15
111-16
115—60—1
127
104
10.1
14
28
15
111-20
115—60—1
127
104
14.4
12
31
20
136-16
115—60—1
127
104
10.1
14
28
15
136-20
115—60—1
127
104
13.3
12
33
20
155-20
115—60—1
127
104
14.0
12
31
20
’Permissible limits of the voltage range at which the unit will operate satisfactorily.
tTime-delay fuse is recommended.
tLength shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Fig. 8—Heating and Cooiing Application Wiring Diagram
A78461
A
WARNING
Never purge a line into a combustion chamber. Never use
matches, candles, flame, or other sources of ignition for the
purpose of checking leakage. Use a soap-and-water solution
to check for leakage. Failure to follow this warning can cause
a fire, explosion, personal injury, or death.
Step 6— Electrical Connections
115-V WIRING — Refer to the unit rating plate or Table 5 for
equipment electrical requirements. The control system requires an
earth ground for proper operation.
A
CAUTION
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.
Make all electrical connections in accordance with the National
Electrical Code ANSI/NFPA 70-1993 and local codes or ordi
nances that might apply. For Canadian installations, all electrical
connections must be made in accordance with CSA C22.1 Cana
dian Electrical Code, or authorities having jurisdiction.
A
WARNING
The cabinet MUST have an uninterrupted or unbroken ground
according to National Electrical Code, ANSI/NFPA 70-1993
and Canadian Electrical Code, CSA C22.1 or local codes to
minimize personal injury if an electrical fault should occur.
This may consist of electrical wire or conduit approved for
electrical ground when installed in accordance with existing
electrical codes. Do not use gas piping as an electrical ground.
The auxiliary junction box can be moved to the right-hand side of
the furnace when a right-side power supply is desired. Remove the
2 screws holding the auxiliary junction box. Mount the junction
box on the right-hand side of the furnace (holes have been
predrilled in casing). The blower door interlock switch must also
be moved to the right side of the furnace due to the length of the
wiring harness. When moved, tuck the wiring harness behind the
clip provided to keep extra wire lengths out of the way.
NOTE:
Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, the microprocessor will ^shut off gas flow
shortly after the completion of ignition trial period.