Recheck the temperature rise. It must be within the limits

specified on the unit rating plate. Recommended operation is

at mid point of rise or above.

3. Set thermostat heat anticipator.

The thermostat heat anticipation must be set to match the amp

draw of the electrical components in the R-W circuit. Accurate

amp draw readings can be obtained at thermostat subbase

terminals R and W. Fig. 13 illustrates an easy method of

obtaining the actual amp draw. The amp reading should be

taken after the blower motor has started. See the thermostat

manufacturer’s instructions for adjusting the heat anticipator

and for varying the heating cycle length.

NOTE:

When using an electronic thermostat, set the cycle rate for

3 cycles per hr.
CHECK SAFETY CONTROLS - The flame sensor, gas valve,

and pressure switch were all checked in the Start-up Procedures

section as part of normal operation.

1. Check primary limit control.

This control shuts off the combustion control system and

energizes the circulating-air blower motor if the furnace

overheats.
The preferred method of checking the limit control is to

gradually block off the return air after the furnace has been

operating for a period of at least 5 minutes. As soon as the

limit has shut off the burners, the return-air opening should be

unblocked. By using this method to check the limit control, it

can be established that the limit is functioning properly and

will operate if there is a motor failure.

2. Check draft safeguard switch.

The purpose of this control is to permit the safe shutdown of

the furnace during certain blocked vent conditions.
a. Disconnect power to furnace and remove vent connector

from furnace outlet collar. Be sure to allow time for vent

pipe to cool down before removing.

b. Restore power to furnace and set room thermostat above

room temperature .

c. After normal start-up, allow furnace to operate for 2

minutes, then block (100 percent) flue outlet. Furnace

should cycle off within 2 minutes.

Fig. 13—Amp Draw check With Ammeter

d. Remove blockage and reconnect vent pipe to furnace outlet

collar.

e. Wait 5 minutes and then reset draft safeguard switch.

3. Check flow-sensing switch.

This control proves operation of draft inducer blower.
a. Turn off 115-v power to furnace.
b. Remove control door and disconnect inducer motor lead

wires from wire harness.

c. Turn on 115-v power to furnace.

,

d. Close thermostat switch as if making normal furnace start.

If the hot surface ignitor does not glow, then the flow­

sensing switch is functioning properly.

e. Turn off 115-v power to furnace.
f. Reconnect inducer motor wires, replace control door, and

turn on 115-v power.

CHECKLIST

1. Put away tools, instruments, and clean up debris.

2. Verify manual reset switches have continuity.
3. Ensure blower and control access doors are properly installed.
4. Cycle test furnace with room thermostat.
5. Check operation of accessories per manufacturer’s instruc­

tions.

6. Review User’s Manual with owner.
7. Leave literature packet near furnace.