Table 7—gas rate (cu ft/hr), Fig. 11—redundant automatic gas control valve, A warning – Carrier WEATHERMAKER 8000 58WAV User Manual
Page 12
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Table 7—Gas Rate (Cu Ft/Hr)
SECONDS
FOR 1
REVOLUTION
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
SIZE OF
TEST DIAL
1
cu ft
360
327
300
277
257
240
225
212
200
189
180
171
164
157
150
144
138
133
129
124
120
116
113
109
106
103
100
97
95
92
90
88
86
84
82
80
78
76
75
73
2
cu ft
720
655
600
555
514
480
450
424
400
379
360
343
327
313
300
288
277
267
257
248
240
232
225
218
212
206
200
195
189
185
180
176
172
167
164
160
157
153
150
147
5
CU ft
1800
1636
1500
1385
1286
1200
1125
1059
100
947
900
857
818
783
750
720
692
667
643
621
600
581
563
545
529
514
500
486
474
462
450
439
429
419
409
400
391
383
375
367
SECONDS
FOR 1
REVOLUTION
50
51
52
53
54
55
56
57
58
59
60
62
64
66
68
70
72
74
76
78
80
82
84
86
88
90
92
94
96
98
100
102
104
106
108
110
112
116
120
SIZE OF
TEST DIAL
1
cu ft
72
71
69
68
67
65
64
63
62
61
60
58
56
54
53
51
50
48
47
46
45
44
43
42
41
40
39
38
38
37
36
35
35
34
33
33
32
31
30
2
cu ft
144
141
138
136
133
131
129
126
124
122
120
116
112
109
106
103
100
97
95
92
90
88
86
84
82
80
78
76
75
74
72
71
69
68
67
65
64
62
60
Table 8—Canadian Orifice Size
5
cu ft
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
164
161
155
150
GAS
SEA LEVEL
0—2000 FT
HIGH ALTITUDE
2001—4500 FT
Natural
43
44
Propane
54
55
2. Set temperature rise.
Do not exceed the temperature rise range specified on the unit
rating plate. Determine the air temperature rise as follows:
a. Place duct thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not "see" heat
exchangers so that radiant heat will not affect thermometer
readings. This is particularly important with straight-run
ducts.
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine tem
perature rise.
- c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease
blower speed to increase temperature rise.
A90044
Fig. 11—Redundant Automatic Gas Control Valve
BURNER FLAME
A
WARNING
Disconnect the electrical power before changing the speed
tap. A failure to follow this warning can cause personal
injury.
d. To change motor speed taps, remove the motor tap lead and
relocate it on the desired terminal on the plug-in terminal
block/speed selector located on the blower housing. (See
Table 9.)
Table 9—Speed Selector
SPEED
TAP NO.*
Common
C
High
1
Med-High
2
Med-Low
3 .
Low
4t
* White wire from control box to common; black wire from control box to cooling
speed selection; red wire from control box to heating and constant fan speed
selection.
tSpped tap No. 4 is not used on 045-08 and 070-08 units.