Carrier 58DR User Manual
Installation, start-up and service instructions, 58dp,dr downflow gas-fired natural-draft furnaces, A caution
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
HEATING« COOLING
58DP,DR
Downflow Gas-Fired Natural-Draft Furnaces
58DP Series 150 and 160
58DR Series 130
Installation, Start-Up and Service Instructions
NOTE:
Read the entire instructions before starting the
installation.
INTRODUCTION
Before installing the furnace, refer to “Procedures for
Natural-Draft Gas-Fired Furnaces” (packaged with the
equipment) for information concerning combustion, venting,
piping, and other standeird installation practices. Further
reference is made to the current edition of the National Fuel
Gas Code NFPA No. 54-1988/ANSI Z223.1-1988.
Reference should also be made to the regulations of the
serving gas supplier and the local building, heating, plumb
ing, or other codes in effect in the area in which the installa
tion is made.
SAFETY CONSIDERATIONS
Installation and servicing of heating equipment can be haz
ardous due to gas and electrical components. Only trained
and qualified personnel should install, repair, or service
heating equipment.
Untrained personnel can perform basic meuntenance func
tions such as cleaning and replacing air filters. AU other
operations must be performed by trained service personnel,
when working on heating equipment, observe precautions in
the literature, tags, and labels attached to or shipped with
the unit and other safety precautions that may apply.
Follow all safety codes, including NFPA No. 54/ANSI
Z223.1-1988, National Fuel Gas Code. Wear safety glasses
and work gloves. Have fire extinguisher available during
startup and adjustment procedures and service call.
Recomized safety information: This is the safety-alert sym
bol
A.
When you see this symbol on the furnace and in
instructions or manueils, be alert to the potential for per
sonal injury.
Understand the signal word—DANGER, WARNING, or
CAUTION. These words are used with the safety-alert sym
bol. DANGER identifies the most serious hazards which
will
result in severe personal injury or death. WARNING
on the other hand
could
result in personal injury or death.
CAUTION is used to identify unsafe practices, which would
result in minor personal injury or product and property
damage.
Each furnace is shipped from the factory completely assem
bled with multispeed direct-drive blower and wired ready for
downflow indoor heating installation only. AU sizes feature
a printed-circuit board control center with easy-to-read, 24-
volt terminal strip to ensure proper connections.
Fig. 1—Model 58DP
Table 1—Clearances (In Inches)
(From Combustible Materials)
Sizes
050
075 thru 150
Sides—Single-Wall Vent
1
1
Type-B Double-Wall Vent
0
1
Back
0
0
Top of Plenum
1
1
Vent Connector—Single-Wall
6
6
Type-B Double-Wall
1
1
Front—Combustion Air*
6
6
Service
30
30
*The 6-inch front clearance is needed for combustion-air entry and
drafthood relief.
»■NOTE:
The furnaces covered by these instructions are
design-certified for use with the vent damper specified on
the furnace rating plate. See instructions packaged with the
vent deunper for its installation.
A CAUTION
Application of this furnace should be indoors with spe
cial attention given to vent sizing and material, gas
input rate, air temperature rise, and unit sizing.
Improper installation or misapplication of the furnace
can require excessive servicing or cause premature com
ponent failure.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
'' I ^
PC 101 Catalog No. 565-873
Printed in U.S.A. Form 58DP,DR-4Si 5/89 Pg 1
Replaces: 58DP,DR-2SI