Winco ASCO 300 Accessory Connectivity Module User Manual
Page 4

Connectivity Module
Installation 1-1
How to Install the Connectivity Module
on 7000 & 4000 Series and Series 300 ATSs
The Connectivity Module mounts on a DIN rail under
the ATS Controller (Group 5 & 1). A short serial cable
connects the Connectivity Module to the Controller. If a
Power Manager is present, a long serial cable connects
the Connectivity Module to the Power Manager. Refer
to installation drawings provided and follow the steps
below to install the Connectivity Module.
Connectivity Module Kit
K754603
for 7000 & 4000 Series
and Series 300 only
Connectivity Module Kit
K754603-001 for
7000 & 4000 Series
and Series 300
with Power Manager
Connectivity
Module 5150
629800-001
Connectivity
Module 5150
629800-001
DIN Rail and
Hardware
754607
DIN Rail and
Hardware
754607
10-in. Serial
Cable for
Controller
629798-001
10-in. Serial
Cable for
Controller
629798-001
4-ft Serial
Cable for
Power
Manager *
629798-002
* A 9-foot serial cable (629798-004) is
required for G7ATB, G7ACTB, G7ADTB.
1. De-energize both Normal and Emergency sources
that feed the ATS. Open enclosure door and check
with a non-contact AC voltage detector.
2. Mount the DIN rail (supplied in the kit) onto two
studs (on the door) below the Controller.
Connectivity Module will mount on the right side.
3. Install Connectivity Module onto DIN rail by
hooking the bottom of module on bottom of DIN rail
and rocking it upward unit it snaps in place.
4. Install the 10-inch serial cable between the
Controller receptacle (J7 on Group 5, J4 on Group 1)
and the Connectivity Module J1 receptacle.
5. If a Power Manager is present, connect the 4-foot
serial cable between the Power Manager J5
receptacle and the Connectivity Module J2
receptacle.*
Now test communications (go to page 1-2).
How to Install the Connectivity Module
on ASCO 940/962 ATSs
The Connectivity Module mounts on a DIN rail near the
ATS Control Panel. A separate power supply is needed
unless it is connected to a Power Manager (PM). Group
6A/7A Control Panel must have a Serial Communication
Kit added. A single communication cable (2 twisted
pairs and overall shield connects the Connectivity
Module to the Control Panel). Refer to installation
drawings provided and follow the steps below to install
the Connectivity Module.
Connectivity Module Kit
K754608
for ASCO 940/962 only
Connectivity Module Kit
K754608-001
for ASCO 940/962 with PM
Connectivity
Module 5150
629800-001
Connectivity
Module 5150
629800-001
DIN Rail and
Hardware
754610
DIN Rail and
Hardware
754610
Serial Com.
Kit for Group
6A/7A CP *
467508
Serial Com.
Kit for Group
6A/7A CP *
467508
Serial Cable
for PM
629798-002
* Serial communication & transient protection boards.
Required
Power Supply **
not supplied
Communication Cable
(4 wires and an overall shield)
not supplied
24 Vdc, 80 mA **
use 16 AWG wire
Belden 9842, 9829, 89729, 82729 or
Alpha 6202C, 6222C, 58902 only
** If a Power Manager (PM) is present, a power supply is not needed
for the Connectivity Module. The serial cable from the Power Manager
provides the power to the Connectivity Module.
1. De-energize both Normal and Emergency sources
that feed the ATS. Open enclosure door and check
with a non-contact AC voltage detector.
2. Mount DIN rail (supplied in the kit) onto two studs
(on the door) below or adjacent to the Control Panel.
3. Install the Connectivity Module onto DIN rail.
4. Prepare and connect the specified communication
cable between the Control Panel terminals and the
Connectivity Module J4 terminals as listed below:
5. Prepare and connect the 24 Vdc power supply to the
Connectivity Module. Use 16 AWG wiring to J5
terminal plug (1 is + positive, 2 is – negative).
Now test communications (go to page 1-2).
To avoid possible shock, burns, or death, deenergize
all electrical sources to the ATS before installing the
Connectivity Module.
DANGER
To avoid possible shock, burns, or death, deenergize
all electrical sources to the ATS before installing the
Connectivity Module.
DANGER